§ 155.413 UTILITY (U).
   (A)   Purpose. This district is intended to accommodate utility uses which are necessary to provide an adequate level of service to meet the current and future needs of the city.
   (B)   Permitted uses. See Table 155.501.
   (C)   Dimensional Standards Table.
Table 155.413: Utility (U)
Standard
Nonresidential
Table 155.413: Utility (U)
Standard
Nonresidential
Minimum Lot Size
5 acres in area [1]
Maximum Lot Coverage
20%
Maximum Height
500 feet
Front Setback
50 feet in depth or width. [2] [3] [4]
Side Setback
50 feet in depth or width. [2] [3] [4]
Rear Setback
50 feet in depth or width. [2] [3] [4]
Street Side Setback
50 feet in depth or width. [2] [3] [4]
Note(s):
[1]   1 A lift station for a sewer line may be located on a lot at least 75 feet wide and 7,500 square feet in area.
[2]   Any structure used as part of a sewage treatment plant, water treatment plant or water pumping plant, including tank, bins, settling basins, reservoirs, and other similar facilities, shall be located at least 100 feet from any lot line.
[3]   Any structure or building exceeding 20 feet in height shall not be located nearer to any property in separate or different ownership than a distance equal to one-half the height of the structure or building.
[4]   On a lot used only for a sewage lift station and having no building over ten feet in height and no structure over 25 feet in height, the required setbacks shall be reduced to 25 feet in depth or width.
 
(Ord. 2021-02, adopted 3-17-21; sought to be reconsidered, Commission passed 4-21-2021)