(A) All structures, including accessory structures, must be elevated on fill so that the lowest floor including basement floor is at or above the regulatory flood protection elevation. The finished fill elevation for structures shall be no lower than one foot below the regulatory flood protection elevation and the fill shall extend at such elevation at least 15 feet beyond the outside limits of the structure erected thereon.
(B) As an alternative to elevation on fill, accessory structures that constitute a minimal investment and that do not exceed 500 square feet at its largest projection may be internally floodproofed in accordance with § 154.043(E) of this chapter.
(C) The storage of any materials or equipment shall be elevated on fill to the regulatory flood protection elevation.
(D) The provisions of § 154.059 of this chapter shall apply.
(Ord. 1475, passed 11-1-2011)