§ 151.10 FIRE ALARM SYSTEMS; SPRINKLER SYSTEMS.
   (A)   Dwellings equipped with or required to have the following systems shall comply with the following requirements:
Type of System
Type of Service
Frequency
To Be Completed by
Type of System
Type of Service
Frequency
To Be Completed by
Detection and alarm
Inspection and testing (low voltage/power limited)
Annual
Qualified employee working for a licensed alarm and communications contractor or licensed electrical contractor
Emergency voice-alarm signaling
Testing and maintenance
Annual
Qualified and knowledgeable persons
Fire pumps
Test pump operation under no-flow conditions
Monthly
Qualified operating personnel
Inspection and testing
Annual
Licensed sprinkler contractor
Portable fire extinguishers
Quick check
Monthly
Minimum knowledge necessary
Maintenance
Annually
Trained person
Smoke control/removal
Testing
Annual
Approved person
Special suppression
Inspection and testing
Annual
Approved persons
Sprinkler
Inspection and testing
Annual
Licensed sprinkler contractor or licensed plumber
Standpipes
Inspection and testing
5 years
Licensed sprinkler contractor or licensed plumber
Systems in high-rise buildings
Testing
Annual
Approved persons
 
   (B)   All fire alarm systems required by the Fire Code shall automatically transmit the alarms to an approved central station, remote or proprietary station as defined in N.F.P.A. 72
(1992 Code, § 460:10) (Ord. 1315, passed 5-20-2003; Ord. passed - -)