1302.03 METAL SHEATH WIRING IN FIRE ZONE ONE; EXCEPTIONS.
   All permanent electrical wiring used for lighting or power in the construction or renovation of all buildings within Fire Zone Number One as set forth in Section 1302.02, except one or two-family residences and buildings ancillary thereto, shall be metal sheath type wiring. Metal sheath type wiring shall also apply to any family residence that occupies any part of a business building or shares a common wall with a business building unless the common wall meets all the requirements for an approved fire wall. Metal sheath type wiring shall consist of rigid conduit electrical metallic tubing (E.M.T. or thinwall) armored cable (B-X), wiremold raceway or greenfield tubing (flexible conduit).