Plans and specifications filed with an application shall be filed in duplicate. Plans shall be drawn to a scale of not less than one-eighth inch (1/8") to the foot, except that for sheds or private garages not more than twelve feet (12') high and of not more than two hundred fifty (250) square feet in area and for ordinary alterations and repairs, scale drawings shall not be required. The plans shall show the location of all sources of water and sewage disposal facilities, the location, character and connection of plumbing and electrical fixtures, the location and dimensions of the foundation, basement or cellar, and of all floors and of the roof, and also show the elevation. Said plans shall also show the means by which storm water shall be drained from said real estate.
All plans and specifications shall be approved by the Building Director and each sheet thereof shall be so stamped before a permit is issued in connection therewith.
No plans and specifications shall be approved for a permit unless such plans are signed and sealed either by an architect licensed to practice architecture by the Illinois Architectural Act or by a structural engineer licensed to practice structural engineering by the Illinois Structural Engineering Act. (225 ILCS 305/1 et seq. and 225 ILCS 340/1 et seq.) (Ord. 330, 7-25-66; Amd. Ord. 4491, 6-15-09)
All fire protection system plans shall be reviewed and approved by the Development Services Department. See Section 5-2-5-2). (Ord. 4491, 6-15-09)