915.10 MONITORING FACILITIES.
   (a)   Each industrial user, as directed by the City, shall install and operate, at the user's own expense, a monitoring facility to allow inspection, sampling and flow measurement of each indirect discharge to the City. Each monitoring facility shall be situated on the industrial user's premises. Where such a location would be impractical or cause undue hardship on the industrial user, the City may concur with the facility being constructed in the public street or sidewalk area, provided the facility is located so that it will be accessible at all times. There shall be ample room in or near such sampling facility to allow accurate sampling and preparation of samples for analysis.
   (b)   The monitoring facility shall have an inspection and sampling manhole or structure with an opening of no less than twenty-four inches in diameter and an internal diameter of no less than forty-eight inches and shall contain such flow measuring, recording and sampling equipment as may be required by the City to ensure compliance with this chapter. The facility and sampling and measuring equipment shall be maintained at all times in a safe and proper operating condition at the expense of the industrial user. All monitoring facilities shall be constructed and maintained in accordance with all applicable local construction standards and specifications.
(Ord. 95-20AC. Passed 4-3-95.)