§ 51.050 SEWER MAIN EXTENSIONS.
   (A)   All regulations promulgated by the State Division of Water Quality and its successors shall be followed and adopted by this reference.
   (B)   In addition to the above, all extensions and sewer services shall also conform to the specifications of the Water Environment Federation (WEF), the American Society of Testing Engineers (ASTM) and other such nationally recognized standards organizations as should apply.
   (C)   All sewer main extensions shall be inspected by video camera, and the locations of all taps recorded on videotape. This inspection shall take place in the presence of town representatives, and representatives of the project engineer. No line extensions shall be accepted without this inspection by camera, and all flaws detected during the camera inspection process being repaired. A DVD recording of this inspection shall be provided to the town.
   (D)   (1)   Where new or upgraded lift stations are required, they shall be designed such that materials, fittings and equipment shall be as deemed by the Utilities Director so as to match materials and supplies currently in use by the town.
      (2)   All such lift stations, or those with added significant flow, shall be provided with the following minimal equipment:
         (a)   An automatic starting, automatic switch over generator fueled by LP (or natural, when available) gas, of sufficient size to operate all of the electrical equipment at the lift station;
         (b)   A radio telemetry system compatible with the existing town system and equipment, including programming and necessary upgrades to the base station to accept the new signals;
         (c)   A basket system for the removal of large solids, rags and the like;
         (d)   A boom and winch operated removal system for both the pumps and basket screenings. This system shall be made of hot dipped galvanized or stainless steel construction;
         (e)   Where the power is available, all pumps shall be 240-volt three-phase operation; and
         (f)   All control panels, cabinets and the like shall be of NEMA 4X stainless steel construction. All hatch type doors shall be of either stainless steel or aluminum construction.
(Ord. passed 5-3-2011; Ord. passed 9-11-2014)