1343.07 CLEARANCES WITH SPECIFIED FORMS OF PROTECTION.
   Stoves may be installed with clearances less than those specified in Table 1 provided the combustible materials is protected as described in Table 2 or Figure 1.
TABLE 2
Clearances, Inches, with Specified Forms of Protection
 
Type of Protection
 
Applied to the   Where the required clearance with no protection is:
combustible mater-
ial unless other-
wise specified and   36 Inches   18 Inches   12 Inches
covering all surfaces
within the
distance specified   Sides Sides Sides
as the required    Above & Connector   Above & Connector   Above & Connector
clearance with no   Rear   Rear    Rear
protection (see
Fig. 1) Thick-
nesses are minimum
                                                                                                                          
 
(a) 1/4 in. transite,
cao wool mill-
board spaced out
1 in.   30   18   30   15   9   12   9   6
(b) 28 gage sheet
metal on 1/4 in.
transite, cao
wool millboard   24   18   24   12   9   12   9   6
Clearances, Inches, with Specified Forms of Protection
 
Type of Protection   Where the required clearance with no protection is:
 
 
            36 Inches      18 Inches      12 Inches
            Sides         Sides         Sides
            Above & Connector   Above & Connector   Above & Connector
            Rear         Rear         Rear
                                                                                                                         
 
(c) 28 gage sheet
metal spaced
out 1 in.         18   12   18   9   6   9   6   4
 
(d) 28 gage sheet
metal on 1/8
in. transite,
cao wool mill-
board spaced
out 1 in.         18   12   18   9   6   9   6   4
 
(e) 1 1/2 in.
transite, cao
wool millboard
cement covering
on heating
appliance         18   12   36   9   6   18   6   4
 
(f) 1/4 in. transite,
cao wool mill-
board on 1 in.
mineral fiber bats
reinforced with
wire mesh or
equivalent         18   12   18   6   6   6   4   4
 
(g) 22 gage sheet
metal on 1 in.
mineral fiber
bats reinforced
with wire or
equivalent         18   12   12   4   3   3   2   2
                                                                                                                                     
   Except for the protection described in subsection (e) hereof, all clearances shall be measured from the outer surface of the appliance to the combustible material disregarding any intervening protection applied to the combustible material.
   Spacers shall be of noncombustible material.
FIGURE 1
 
A equals the required clearance with no protection, specified in Table 1.
B equals the reduced clearance in accordance with Table 2. The protection applied to the construction using combustible material should extend far enough in each direction to make C equal to A.
(Ord. 1984-17. Passed 5-15-84.)