§ 53.08 PREVENTION DEVICES.
   (A)   Any backflow prevention device required by these rules and regulations shall be of a model or construction approved by the village and the Director and shall comply with the following:
      (1)   An air gap separation, to be approved, shall be at least twice the diameter of the supply pipe, measured vertically above the top rim of the vessel, but in no case less than one inch.
      (2)   A double check valve assembly or a reduced pressure principle backflow prevention device shall be approved by the village.
      (3)   An interchangeable connection, to be approved, shall be either a swing type connector or a four-way valve of the lubricated plug type that operates through a mechanism which unseats the plug, turns it 90 degrees and reseats the plug. Four-way valves shall not be used as stop valves but must have separate stop valves on each pipe connected to the valve. The telltale port on the four-way valve shall have no piping connected and the threads or flange on this port shall be destroyed so that a connection cannot be made.
   (B)   Existing backflow prevention devices approved by the village or the Director of the Ohio Environmental Protection Agency at the time of installation and properly maintained shall, except for inspection, testing and maintenance requirements, be excluded from the requirement of division (A) of this section providing the village is assured that they will satisfactorily protect the public potable water system. Whenever the existing device is moved from the present location or requires more than minimum maintenance or when the village finds that the maintenance of the device constitutes a hazard to health, the device shall be replaced by a backflow prevention device meeting the requirement of these regulations.
(Ord. 2010-8-20, passed 9-14-10)