§ 150.01 ELECTRICAL RULES AND REGULATIONS.
   (A)   All electrical wiring and all electrical installations and all repairs to either of the same in or upon any buildings, structures and premises in the county, except for the incorporated areas of Martinsville and Mooresville, shall conform to the requirements of this code and section.
   (B)   All electrical equipment and installations shall be in conformity with such approved standards for safety to life and property as are generally recognized and used in this state and expressed in the standards herein adopted.
   (C)   Conformity with the rules, regulations and standards prescribed in the September 1959 National Electrical Code published in November 1959 (NBFU #70), being the rules, regulations and standards of the National Board of Fire Underwriters for Electrical Wiring and Apparatus, two copies of which have been filed with this section in the office of the Auditor of the county, and are to be kept there for public inspection and which are hereby incorporated in this section and made a part thereof by this reference thereto, as fully as though re-copied herein and which are hereby adopted as the electrical rules and regulations of this section which shall be prima facie evidence of conformity with approved standards for safety to life and property.
   (D)   In addition to the above referred- to Electrical Code, the following rules and regulations are hereby adopted.
      (1)   Service entrance equipment for all new single and two-family residences where construction is started after effective date of this section shall be rated not less than 100 amperes.
         (a)   The service equipment shall be rated 100 amperes 120/240 volts 3-wire solid neutral with 100 amperes main fused disconnect or 100 ampere circuit breaker. If any portion of the building of over 500 square feet is to be occupied before the building is completed, the service entrance equipment must be 100 amperes at the start.
         (b)   Service entrance conductors shall be a minimum of two #2 copper type RH, RW or TW and one #4 bare copper stranded neutral or equivalent except that SW copper #6 entrance cable or equivalent will be permitted with 60 ampere service equipment.
      (2)   For trailers and occupancies other than residential, the service equipment shall be a minimum of 60 amperes, if a switch is used, or 50 amperes if a breaker is used; however, for installations consisting of not more than one 2-wire branch circuit, a switch or circuit breaker of 30 ampere rating may be used.
      (3)   Service entrance conductors shall have a carrying capacity of not less than the rating of the service entrance equipment.
      (4)   On 120/240 volt three-phase four-wire delta services for combination 240-volt, three-phase power and 120/240 single-phase lighting, the phase conductor having higher voltage to ground shall be either a red coded wire or identified with red glyptal paint or equivalent.
         (a)   All phase wires of the service conductors shall be of equal size.
         (b)   Each separately metered installation shall be equipped with an approved circuit switch or circuit breaker.
      (5)   All insulated wires shall be plainly marked as to the type and size.
      (6)   “BX” type cable shall not be used.
      (7)   The service and meter locations are subject to the approval of the utility providing the electric service.
      (8)   Range circuits for domestic ranges shall be a minimum of three #6 copper conductors.
      (9)   Motor units on fossil fuel heating equipment must be installed on separate circuits.
      (10)   Non-metallic sheathed cable installed below the ceiling line in basements shall be protected where exposed to mechanical or physical injury.
      (11)   All domestic water supply pumps shall be equipped with an approved disconnect switch.
      (12)   No electric water heater or clothes dryer will be served with smaller wire than #10 AWG copper wire.
         (a)   No electric hot water heater shall be serviced with electricity until the following is installed: an approved pressure relief valve on the cold water line, or an approved temperature relief valve on the hot water line, or an approved combination pressure and temperature relief valve on the hot water line, with the temperature-sensing element in the top of the tank.
         (b)   All electric water heaters and clothes dryers shall be properly grounded.
      (13)   All wiring for light and power shall be installed so as to make all raceways, outlet boxes, and equipment grounded, in accordance with the National Electrical Code.
      (14)   Recessed fixtures shall not be used as junction boxes.
      (15)   All service equipment, distribution and control switches shall be readily accessible as defined in the National Electrical Code.
      (16)   All sump pumps shall be grounded in an approved manner.
      (17)   The grounding conductor must be connected to the city water piping system, if one is available.
         (a)   If a city water system is not available, an approved one-half inch in diameter by ten feet in length copper-weld ground rod shall be used for grounding purposes.
         (b)   If there is a domestic water supply system with any metallic water piping on the premises, this piping shall be grounded to the common neutral ground of the customer service entrance equipment with not less than #6 copper wire. Any rubber or plastic hose connections in the metallic piping system shall be electrically bonded.
      (18)   Ground clamps on water piping of copper, brass or lead shall be of copper, and those for use on galvanized or iron pipe should be of galvanized iron and so designed that they will avoid mechanical injury to the pipe.
      (19)   Where the necessity for the temporary use of electric current in any installation is shown to exist, or the temporary use of electrical current is needed during the construction or altering of any building, the Inspector may grant permission for such temporary wiring or apparatus or fixture for a period not exceeding 120 days; however, extension may be granted by the Inspector.
   (E)   Whenever any of the aforesaid sets of rules, regulations and standards so incorporated herein by reference thereto in the foregoing divisions (C) and (D) above may be hereinafter amended or supplemented and whenever such changes in all or any thereof are adopted by any later ordinance and two copies of any such amended or supplemented rules, regulations and standards or lists are filed with the County Auditor and kept by him or her as aforesaid, any or all of such changed rules, regulations and standards or lists shall thereupon also become a part of this code.
   (F)   After the effective date of this section, no person, persons or corporations shall install any electrical wiring or electrical installation or make any repairs or either of the same except in accordance with the aforesaid code.
   (G)   No person, persons or corporation shall use any electrical device installed in violation of this section; however, all electric utilities shall be exempt from the terms of this section and their operation shall be controlled and in conformity with the existing National Electrical Code as the same effects their operations in providing service to their customers.
   (H)   The Executive Secretary of the County Plan Commission shall administer and enforce this section, including the inspection and approval of all electrical wiring and installation and repairs of the same and no electrical wiring shall be approved by such Executive Secretary, except where the provisions of this section shall have been complied with.
   (I)   No electrical service shall be made unless a permit has been issued for such service by the Executive Secretary of the County Plan Commission.
      (1)   The permit can be obtained at the County Plan Commission office in the County Courthouse by either the contractor or the customer.
      (2)   The inspector will place an inspection tag on the service connection after inspection is made and passed.
      (3)   On all interior branch circuit conductors, nothing smaller than 12/2 romex will be accepted; however, due to recent manufacture of many appliances being equipped with the three-prong grounding type plug, it is highly recommended that 12/2 romex with ground be used. BX or armored cable will not be accepted under any circumstance. It is also suggested that on kitchen appliance circuits, number 10/2 with ground be used.
   (J)   It shall be a violation of this section for any person or corporation to use any electrical device installed subsequent to the date of this section if said electrical device has not been inspected and approved by the Executive Secretary.
   (K)   As used in this section, the term electrical device shall include all manner of electrical wiring and power installations of every sort and character.
   (L)   The Executive Secretary will maintain records showing what structures and installations as concerned in this section have been inspected by him or her.
   (M)   Inspection fees to be collected by the Executive Secretary for the electrical service inspection are hereby established as follows:
      (1)   Wiring for branch circuits (roughing-in):
         (a)   One circuit: $2; for each additional circuit up to and including 20, add $0.50;
         (b)   Twenty circuits: $20; for each additional circuit more than 20 add $0.25; and
         (c)   A three-wire circuit is considered the same as two 2-wire circuits.
      (2)   Motors, generators and the like (or feeders for same, if entire installation is not complete):
         (a)   Over two and one-half HP (horsepower) to ten HP: $2;
         (b)   Over ten HP to 20 HP: $3;
         (c)   Over 20 HP to 50 HP: $4;
         (d)   Over 50 HP: $5;
         (e)   Each additional motor, device or machine covered by the same inspection as follows:
            1.   Over two and one-half HP to ten HP: $1.50;
            2.   Over ten HP to 20 HP: $2;
            3.   Over 20 HP to 50 HP: $2.50; and
            4.   Over 50 HP: $3.
         (f)   Note: wherever horsepower is referred to in this division (M)(2), the same shall be construed as horsepower or kilowatt as the case may be.
      (3)   Stoves, welders, rectifiers, trans-formers, switchboards, and miscellaneous devices: apply motor schedule:
         (a)   Minimum fee for stoker motor: $1.50; and
         (b)   Minimum fee for heaters and ranges (more than 660 watts): $2.
      (4)   Reinspection fees (to apply to reinspection of old work when requested by contractors and owners, also for re-inspections made necessary by defects):
         (a)   One circuit: $2; to which add $0.25 for each additional circuit up to and including ten; and
         (b)   Ten circuits: $3.75, to which add $0.15 for each additional, more than ten.
      (5)   Service entrance only:
         (a)   Two-wire service: $2;
         (b)   Three-wire service: $2.50;
         (c)   Four-wire service: $3; and
         (d)   No charge for services when job consists of circuits or connected load.
(Ord. 5-1-1, passed 12-6-1960)