§ 15.04.440 VARIOUS AMENDMENTS ADOPTED.
   Section R301.1.3.2 of the 2022 Edition of the California Residential Code is amended to read as follows:
      R301.1.3.2 Woodframe structures greater than two-stories. The building official shall require construction documents to be approved and stamped by a California licensed architect or engineer for all dwellings of woodframe construction more than two stories and basement in height located in Seismic Design Category A, B or C. Notwithstanding other sections of law; the law establishing these provisions is found in Business and Professions Code Sections 5537 and 6737.1.
   The building official shall require construction documents to be approved and stamped by a California licensed architect or engineer for all dwellings of woodframe construction more than one story in height or with a basement located in Seismic Design Category D0, D1, or D2.
   Section R301.1.5 is added to Chapter 3 of the 2022 Edition of the California Residential Code to read as follows:
   R301.1.5 Seismic design provisions for buildings constructed on or into slopes steeper than one unit vertical in three units horizontal (33.3 percent slope). The design and construction of new buildings and additions to existing buildings when constructed on or into slopes steeper than one unit vertical in three units horizontal (33.3 percent slope) shall comply with Section 1613.6 of the California Building Code.
   Items 1, 3 and 5 of Section R301.2.2.6 of the 2022 Edition of the California Residential Code are amended to read as follows:
   1.   Shear wall or braced wall offsets out of plane. Conditions where exterior shear wall lines or braced wall panels are not in one plane vertically from the foundation to the uppermost story in which they are required.
      Exception: For wood light-frame construction, floors with cantilevers or setbacks not exceeding four times the nominal depth of the wood floor joists are permitted to support braced wall panels that are out of plane with braced wall panels below provided that all of the following are satisfied:
         1.   Floor joists are nominal 2 inches by 10 inches (51 mm by 254 mm) or larger and spaced not more than 16 inches (406 mm) on center.
         2.   The ratio of the back span to the cantilever is not less than 2 to 1.
         3.   Floor joists at ends of braced wall panels are doubled.
         4.   For wood-frame construction, a continuous rim joist is connected to ends of cantilever joists. When spliced, the rim joists shall be spliced using a galvanized metal tie not less than 0.058 inch (1.5 mm) (16 gage) and 1 1/2 inches (38 mm) wide fastened with six 16d nails on each side of the splice or a block of the same size as the rim joist of sufficient length to fit securely between the joist space at which the splice occurs fastened with eight 16d nails on each side of the splice; and
         5.   Gravity loads carried at the end of cantilevered joists are limited to uniform wall and roof loads and the reactions from headers having a span of 8 feet (2438 mm) or less.
   3.   Shear wall or braced wall offsets in plane. Conditions where the end of a braced wall panel occurs over an opening in the wall below. and ends at a horizontal distance greater than 1 foot (305 mm) from the edge of the opening. This provision is applicable to shear walls and braced wall panels offset in plane and to braced wall panels offset out of plane as permitted by the exception to item 1.
      Exception: For wood light-frame wall construction, one end of a braced wall panel shall be permitted to extend more than one foot (305 mm) over an opening not more than 8 feet (2438 mm) in width in the wall below provided that the opening includes a header in accordance with all of the following:
         1.   The building width, loading condition and framing member species limitations of Table R602.7(1) shall apply.
         2.   The header is composed of:
            2.1   Not less than one 2x12 or two 2x10 for an opening not more than 4 feet (1219 mm) wide.
            2.2   Not less than two 2x12 or three 2x10 for an opening not more than 6 feet (1829 mm) in width.
            2.3   Not less than three 2x12 or four 2x10 for an opening not more than 8 feet (2438 mm) in width.
         3.   The entire length of the braced wall panel does not occur over an opening in the wall below.
   5.   Floor level offset. Conditions where portions of a floor level are vertically offset.
      Exceptions:
         1.   Framing supported directly by continuous foundations at the perimeter of the building.
         2.   For wood light-frame construction, floors shall be permitted to be vertically offset where the floor framing is lapped or tied together as required by section R502.6.1.
   Section R301.2.2.11 is added to Chapter 3 of the 2022 Edition of the California Residential Code to read as follows:
   R301.2.2.11 Anchorage of mechanical, electrical, or plumbing components and equipment. Mechanical, electrical, or plumbing components and equipment shall be anchored to the structure. Anchorage of the components and equipment shall be designed to resist loads in accordance with the California Building Code and ASCE 7, except where the component is positively attached to the structure and flexible connections are provided between the component and associated ductwork, piping, and conduit; and either
      1.   The component weighs 400 lb (1,780 N) or less and has a center of mass located 4 ft (1.22 m) or less above the supporting structure; or
      2.   The component weighs 20 lb (89N) or less or, in the case of a distributed system, 5 lb/ft (73 N/m) or less.
   Section R401.1 of the 2022 Edition of the California Residential Code is amended to read as follows:
   R401.1 Application. The provisions of this chapter shall control the design and construction of the foundation and foundation spaces for buildings. In addition to the provisions of this chapter, the design and construction of foundations in flood hazard areas as established by Table R301.2 shall meet the provisions of Section R322. Wood foundations shall be designed and installed in accordance with AWC PWF.
      Exception: The provisions of this chapter shall be permitted to be used for wood foundations only in the following situations:
         1.   In buildings that have no more than two floors and a roof.
         2.   When interior basement and foundation walls are constructed at intervals not exceeding 50 feet (15 240 mm).
      Wood foundations in Seismic Design Category D0, D1, or D2 shall be designed in accordance with accepted engineering practice not be permitted.
      Exception: In non-occupied, single-story, detached storage sheds and similar uses other than carport or garage, provided the gross floor area does not exceed 200 square feet, the plate height does not exceed 12 feet in height above the grade plane at any point, and the maximum roof projection does not exceed 24 inches.
   Sections R403.1.2, R403.1.3.6 and R403.1.5 of the 2022 Edition of the California Residential Code are amended to read as follows:
   R403.1.2 Continuous footing in Seismic Design Categories D0, D1 and D2. Exterior walls of buildings located in Seismic Design Categories D0, D1 and D2 shall be supported by continuous solid or fully grouted masonry or concrete footings. Other footing materials or systems shall be designed in accordance with accepted engineering practice. Required interior braced wall panels in buildings located in Seismic Design Categories D0, D1 and D2 with plan dimensions greater than 50 feet (15 240 mm) shall be supported by continuous solid or fully grouted masonry or concrete footings in accordance with Section R403.1.3.4, except for two-story buildings in Seismic Design Category D2, in which all braced wall panels, interior and exterior, shall be supported on continuous foundations.
      Exception: Two-story buildings shall be permitted to have interior braced wall panels supported on continuous foundations at intervals not exceeding 50 feet (15 240 mm) provided that:
         1.   The height of cripple walls does not exceed 4 feet (1219 mm).
         2.   First-floor braced wall panels are supported on doubled floor joists, continuous blocking or floor beams.
         3.   The distance between bracing lines does not exceed twice the building width measured parallel to the braced wall line.
   R403.1.3.6 Isolated concrete footings. In detached one- and two-family dwellings located in Seismic Design Category A, B, or C, that are three stories or less in height, and constructed with stud bearing walls, isolated plain concrete footings supporting columns or pedestals are permitted.
   R403.1.5 Slope. The top surface of footings shall be level. The bottom surface of footings shall not have a slope exceeding one unit vertical in 10 units horizontal (10-percent slope). Footings shall be stepped where it is necessary to change the elevation of the top surface of the footings or where the slope of the bottom surface of the footings will exceed one unit vertical in 10 units horizontal (10-percent slope).
      For structures assigned to Seismic Design Categories D0, D1 or D2, stepped footings shall be reinforced with four No. 4 rebar. Two bars shall be place at the top and bottom of the footings as shown in Figure R403.1.5.
 
   FIGURE R403.1.5
   STEPPED FOOTING
   Section R404.2 of the 2022 Edition of the California Residential Code is amended to read as follows:
   R404.2 Wood foundation walls. Wood foundation walls shall be constructed in accordance with the provisions of Sections R404.2.1 through R404.2.6 and with the details shown in Figures R403.1(2) and
   R403.1(3). Wood foundation walls shall not be used for structures located in Seismic Design Category D0, D1 or D2.
   Section R501.2 of the 2022 Edition of the California Residential Code is amended to read as follows:
   R501.2 Requirements. Floor construction shall be capable of accommodating all loads in accordance with Section R301 and of transmitting the resulting loads to the supporting structural elements. Mechanical or plumbing fixtures and equipment shall be attached or anchored to the structure in accordance with Section R301.2.2.11.
   Section R503.2.4 is added to Chapter 5 of the 2022 Edition of the California Residential Code to read as follows:
   R50 3.2.4 Openings in horizontal diaphragms. Openings in horizontal diaphragms with a dimension perpendicular to the joist that is greater than 4 feet (1.2 m) shall be constructed in accordance with Figure R503.2.4.
 
   a.   Blockings shall be provided beyond headers.
   b.   Metal ties not less than 0.058 inch [1.47 mm (16 galvanized gage)] by 1.5 inches (38 mm) wide with eight 16d common nails on each side of the header-joist intersection. The metal ties shall have a minimum yield of 33,000 psi (227 MPa).
   c.   Openings in diaphragms shall be further limited in accordance with Section R301.2.2.6.
FIGURE R503.2.4
OPENINGS IN HORIZONTAL DIAPHRAGMS
   Lines 20, 21, 24, and 34 - 37 of Table R602.3(1) of the 2022 Edition of the California Residential Code are amended to read as follows:
   TABLE R602.3(1)-continued FASTENING SCHEDULE
ITEM
DESCRIPTION OF BUILDING ELEMENTS
NUMBER AND TYPE OF FASTENERS a, b, c
SPACING AND LOCATION
ITEM
DESCRIPTION OF BUILDING ELEMENTS
NUMBER AND TYPE OF FASTENERS a, b, c
SPACING AND LOCATION
 
20 k
 
1" x 6" sheathing to each bearing
3-8d box (2 ½" x 0.113"); or
2-8d common (2 ½" x 0.131"); or
2-10d box (3" x 0.128"); or
2 staples, 1" crown, 16 ga., 1-3/4" long
   Face nail
21 k
1" x 8" and wider sheathing to each bearing
3-8d box (2 ½" x 0.113"); or
3-8d common (2 ½" x 0.131"); or
3-10d box (3" x 0.128"); or
3 staples, 1" crown, 16 ga., 1-3/4" long
   Face nail
Wider than 1" x 8"
4-8d box (2 ½" x 0.113"); or
3-8d common (2 ½" x 0.131"); or
3-10d box (3" x 0.128"); or
4 staples, 1" crown, 16 ga., 1-3/4" long
Floor
24 k
1" x 6" subfloor or less to each joist
3-8d box (2 ½" x 0.113"); or
2-8d common (2 ½" x 0.131"); or
3-10d box (3" x 0.128"); or
2 staples, 1" crown, 16 ga., 1-3/4" long
   Face nail
Other wall sheathing g
34 k
½" structural cellulosic fiberboard sheathing
1-1/2" x 0.120" galvanized roofing nail, 7/16" head diameter, or 1-1/4" long 16 ga. staple with 7/16" or 1" crown
3
6
35 k
25/32" structural cellulosic fiberboard sheathing
1-3/4" x 0.120" galvanized roofing nail, 7/16" head diameter, or 1-1/4" long 16 ga. staple with 7/16" or 1" crown
3
6
36 k
½" gypsum sheathing d
1-1/2" x 0.120" galvanized roofing nail, 7/16" head diameter, or 1-1/4" long 16 ga.;
staple galvanized, 1-1/2" long; 7/16" or 1" crown or 1-1/4" screws, Type W or S
7
7
37 k
5/8" gypsum sheathing d
1-3/4" galvanized roofing nail, 7/16" head diameter, or 1-1/4" long 16 ga.;
staple galvanized, 1-1/2" long; 7/16" or 1" crown or 1-1/4" screws, Type W or S
7
7
 
   TABLE R602.3(1)-continued FASTENING SCHEDULE
k.   Use of staples in roof, floor, and braced wall panels shall be prohibited in Seismic Design Category D0, D1, or D2
   Exception of Section R602.3.2 and Table R602.3.2 of the 2022 Edition of the California Residential Code is amended to read as follows:
   Exception: A In other than Seismic Design Category D0, D1 or D2, a single top plate used as an alternative to a double top plate shall comply with the following:
      1.   The single top plate shall be tied at corners, intersecting walls, and at in-line splices in straight wall lines in accordance with Table R602.3.2.
      2.   The rafters or joists shall be centered over the studs with a tolerance of not more than 1 inch (25 mm).
      3.   Omission of the top plate is permitted over headers where the headers are adequately tied to adjacent wall sections in accordance with Table R602.3.2.
 
   Footnote "b" of Table R602.3(2) of the 2022 Edition of the California Residential Code is amended to read as follows:
   b.   Staples shall have a minimum crown width of 7/16-inch on diameter except as noted. Use of staples in roof, floor, subfloor, and braced wall panels shall be prohibited in Seismic Design Category D0, D1, or D2.
   Section R602.10.2.3 of the 2022 Edition of the California Residential Code is amended to read as follows:
   R602.10.2.3 Minimum number of braced wall panels. Braced wall lines with a length of 16 feet (4877 mm) or less shall have not less than two braced wall panels of any length or one braced wall panel equal to 48 inches (1219 mm) or more. Braced wall lines greater than 16 feet (4877 mm) shall have not less than two braced wall panels. In Seismic Design Category D0, D1, or D2, no braced wall panel shall have a contributing length less than 48 inches in length or as required in Section R602.10.3, whichever is greater.
   Table R602.10.3(3) of the 2022 Edition of the California Residential Code is amended to read as follows:
 
 
   a.   Linear interpolation shall be permitted.
   b.   Wall bracing lengths are based on a soil site class "D." Interpolation of bracing length between the Sds values associated with the seismic design categories shall be permitted when a site-specific Sds value is determined in accordance with Section 1613.2 of the California Building Code.
   c.   Where the braced wall line length is greater than 50 feet, braced wall lines shall be permitted to be divided into shorter segments having lengths of 50 feet or less, and the amount of bracing within each segment shall be in accordance with this table.
   d.   Method LIB shall have gypsum board fastened to not less than one side with nails or screws in accordance with Table R602.3(1) for exterior sheathing or Table R702.3.5 for interior gypsum board. Spacing of fasteners at panel edges shall not exceed 8 inches.
   e.   Methods PFG and CS-SFB do not apply in Seismic Design Categories D0, D1 and D2.
   f.   Methods PFH, PFG and ABW are only permitted on a single story or a first of two stories.
   g.   Where more than one bracing method is used, mixing methods shall be in accordance with Section R602.10.4.1.
   h.   One- and two- family dwellings in Seismic Design Category D2 exceeding two stories shall be designed in accordance with accepted engineering practice.
   i.   Methods GB and PCP braced wall panel h/w ratio shall not exceed 1:1 in SDC D0, D1 and D2. Methods DWB, SFB, PBS, HPS, and CS-SFB are not permitted in D0, D1 and D2.
   Table R602.10.4 of the 2022 Edition of the California Residential Code is amended to read as follows:
 
   Table R602.10.5 of the 2022 Edition of the California Residential Code is amended to read as follows:
 
   For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 mile per hour = 0.447 m/s.
   NP = Not Permitted.
   a.   Linear interpolation shall be permitted.
   b.   Use the actual length where it is greater than or equal to the minimum length.
   c.   Maximum header height for PFH is 10 feet in accordance with Figure R602.10.6.2, but wall height shall be permitted to be increased to 12 feet with pony wall.
   d.   Maximum header height for PFG is 10 feet in accordance with Figure R602.10.6.3, but wall height shall be permitted to be increased to 12 feet with pony wall.
   e.   Maximum header height for CS-PF is 10 feet in accordance with Figure R602.10.6.4, but wall height shall be permitted to be increased to 12 feet with pony wall.
   Figure R602.10.6.1 of the 2022 Edition of the California Residential Code is amended to read as follows:
 
 
   Figure R602.10.6.2 of the 2022 Edition of the California Residential Code is amended to read as follows:
 
   Figure R602.10.6.4 of the 2022 Edition of the California Residential Code is amended to read as follows:
 
   Section R606.4.4 of the 2022 Edition of the California Residential Code is amended to read as follows:
   R606.4.4 Parapet walls. Unreinforced solid masonry parapet walls shall not be less than 8 inches (203 mm) thick and their height shall not exceed four times their thickness. Unreinforced hollow unit masonry parapet walls shall be not less than 8 inches (203 mm) thick, and their height shall not exceed three times their thickness. Masonry parapet walls in areas subject to wind loads of 30 pounds per square foot (1.44 kPa) or located in Seismic Design Category D0, D1 or D2, or on townhouses in Seismic Design Category C shall be reinforced in accordance with Section R606.12.
   Section R606.12.2.2.3 of the 2022 Edition of the California Residential Code is amended to read as follows:
   R606.12.2.2.3 Reinforcement requirements for masonry elements. Masonry elements listed in Section R606.12.2.2.2 shall be reinforced in either the horizontal or vertical direction as shown in Figure R606.11(2) R606.11(2) and in accordance with the following:
      1.   Horizontal reinforcement. Horizontal joint reinforcement shall consist of not less than two longitudinal W1.7 wires spaced not more than 16 inches (406 mm) for walls greater than 4 inches (102 mm) in width and at least one longitudinal W1.7 wire spaced not more than 16 inches (406 mm) for walls not exceeding 4 inches (102 mm) in width; or not less than one No. 4 bar spaced not more than 48 inches (1219 mm). Where two longitudinal wires of joint reinforcement are used, the space between these wires shall be the widest that the mortar joint will accommodate. Horizontal reinforcement shall be provided within 16 inches (406 mm) of the top and bottom of these masonry elements.
      2.   Vertical reinforcement. Vertical reinforcement shall consist of not less than one No. 4 bar spaced not more than 48 inches (1219 mm). Vertical reinforcement shall be within 168 inches (406203 mm) of the ends of masonry walls.
   Section R803.2.4 is added to Chapter 8 of the 2022 Edition of the California Residential Code to read as follows:
   R803.2.4 Openings in horizontal diaphragms. Openings in horizontal diaphragms shall conform with Section R503.2.4.
   Section R1001.3.1 of the 2022 Edition of the California Residential Code is amended to read as follows:
   R1001.3.1 Vertical reinforcing. For chimneys up to 40 inches (1016 mm) wide, four No. 4 continuous vertical bars adequately anchored into the concrete foundation shall be placed between wythes of solid masonry or within the cells of hollow unit masonry and grouted in accordance with Section R606. Grout shall be prevented from bonding with the flue liner so that the flue liner is free to move with thermal expansion. For chimneys more than 40 inches (1016 mm) wide, two additional No. 4 vertical bars adequately anchored into the concrete foundation shall be provided for each additional flue incorporated into the chimney or for each additional 40 inches (1016 mm) in width or fraction thereof.
(Ord. 2010-16 § 1, 2010; Ord. 2013-05 § 1, 2013; Ord. 2016-12 § 3, 2016; Ord. 2019-11 § 3, 2019; Ord. 2022-09, § 3(part), 2022)