Section 903.3.1.3 of the Building Code is hereby amended to read as follows:
Where allowed in buildings of Group R, automatic sprinkler systems shall be installed throughout in accordance with NFPA 13D with the following additions:
(a) Attics containing forced air units shall have one or more quick-response intermediate temperature sprinkler heads adjacent to each unit.
(b) Private garages shall be sprinklered and shall have a design density of an Ordinary Hazard Group 1 occupancy with a design area of two (2) heads. Quick-response intermediate temperature commercial type heads shall be used for the garage area.
(c) Attics and basements used for storage purposes shall be fully sprinklered with residential type heads.
(d) A single exterior bell activated by the waterflow switch shall be provided at an approved location.
(Ord. 2013-05 § 1, 2013)