§ 15.04.250 SECTION 903.3.1.2 AMENDED - NFPA 13R SPRINKLER SYSTEM.
   Section 903.3.1.2 of the Building Code is hereby amended to read as follows:
      Where allowed in buildings of Group R, up to and including buildings four stories in height, automatic sprinkler systems shall be installed throughout in accordance with NFPA 13R with the following additions:
      (a)   Attics shall be fully sprinklered with quick-response intermediate temperature heads.
      (b)   Private garages shall be sprinklered and shall have a design density of an Ordinary Hazard Group 1 occupancy with a design area of two (2) heads. Quick-response intermediate temperature commercial type heads shall be used for the garage area.
(Ord. 2013-05 § 1, 2013)