§ 15.04.245 SECTION 903.2.18 AMENDED-GROUP U PRIVATE GARAGES AND CARPORTS ACCESSORY TO GROUP R-3 OCCUPANCIES.
   Section 903.2.18 of the Building Code is hereby amended to read as follows:
      Carports with habitable space above, detached private garages over 1000 square feet in area, and attached private garages shall be protected by fire sprinklers in accordance with this section. These areas shall have a design density of an Ordinary Hazard Group 1 occupancy with a design area of two (2) heads. Quick-response intermediate temperature commercial type heads shall be used.
(Ord. 2013-05 § 1, 2013)