Section 6112 is hereby added to the California Fire Code 2022 Edition to read as follows:
1. All individual containers shall be a maximum size of 500-gallon (1893 L) water capacity. Multiple container systems shall not exceed 500-gallons (1893 L) in aggregate quantity.
2. A minimum 10 foot setback shall be maintained between the tank and all buildings in perpetuity. All future developments on the property shall be subject to this requirement.
3. Signage shall be provided on the tank indicating its contents and also warning of "NO SMOKING WITHIN 25 FEET".
4. Weeds, grass, brush, trash, and other combustible materials shall be kept a minimum of 10 feet from the tank.
5. A minimum 6A:80BC fire extinguisher shall be provided within 50 feet of the tank. It shall be the applicant's responsibility to have the fire extinguisher serviced by a qualified contractor on an annual basis.
6. During refueling, the LP tank vehicle shall not be left unattended at any time.
(Ord. 2013-05 § 2, 2013; Ord. 2019-11 § 4, 2019; Ord. 2022-09 § 4 (part), 2022)