§ 15.20.150 SECTION 903.3.1.3 AMENDED—NFPA 13D SPRINKLER SYSTEM.
   Section 903.3.1.3 of the Fire Code is hereby amended to read as follows:
   903.1.3 Where allowed in buildings of Group R, automatic sprinkler systems shall be installed throughout in accordance with NFPA 13D as amended by Chapter 80 with the following additions:
      (a)   Attics containing forced air units shall have one or more quick-response intermediate temperature sprinkler heads adjacent to each unit.
      (b)   Private garages shall be sprinklered and shall have a design density of an Ordinary Hazard Group 1 occupancy with a design area of two (2) heads. Quick-response intermediate temperature commercial type heads shall be used for the garage area.
      (c)   Attics and basements used for storage purposes shall be fully sprinklered with residential type heads.
      (d)   A single exterior bell activated by the waterflow switch shall be provided at an approved location.
      (e)   A representative sample of spare fire sprinkler heads shall be provided at an approved location.
(Ord. 2007-17, § 1 (part), 2007; Ord. 2013-05 § 2, 2013; Ord. 2019-11 § 4, 2019; Ord. 2022-09 § 4 (part), 2022)