1424.03 INSTALLATION RULES FOR WATER, SERVICE AND METERS; APPLICATION OF OHIO PLUMBING CODE.
   (a)   Size. No water service for any building or structure shall be less in size than three- quarters of an inch (inside diameter). No three-quarter inch service shall exceed 120 feet in length.
(Ord. 2528. Passed 4-5-77.)
   (b)   Kind of Pipe. All pipe and fittings used for water service from the curb cock on installations where the meter is on the inside, and from meter bar where the meter is on the outside, to the main stop, shall conform to the Ohio Plumbing Code, referred to in Section 1424.01(e).
   Water service pipe and fittings extending from the water main and to the curb cock shall conform to the regulation of the administrative authority having jurisdiction over the public water supply system.
   Subject to the above, the minimum size for a water service pipe shall be three-quarters of an inch.
   A separate service and water meter shall be run for each family unit contained in a duplex or multiple-dwelling up to, but not including, three or more units. Where the building contains more than two units, the water service pipe shall be sized and designed in accordance with accepted engineering practice and the approval of the Plumbing Inspector.
(Ord. 3048. Passed 9-2-80.)
   (c)   Demand Load. The demand load in the building water supply system shall be based on the number and kind of fixtures installed and the probable simultaneous use of these fixtures, in accordance with accepted engineering practice.
   (d)   Installation of Service. All meters shall be installed in approved water meter pits between the curb and gutter, except for commercial buildings.
   The water service pipe shall be installed not less than forty-two inches below the finished grade at all points of the lot between the curb cock and the building foundation.
    A distance of not less than ten feet shall be maintained from all sewers, leeching fields, septic tanks, leeching wells or any other source of contamination. However, a water service may be installed in the same ditch as the sewer if a distance of not less than two feet above the sewer can be maintained, and the water service shall be placed on a bench shelf that shall be provided or cut into the side of the trench so that no part of the water service will be laid on filled soil.
   When slab or crawl space-type of construction is encountered, the water service shall be so installed that a depth of not less than forty-two inches and a distance of six inches or more inside from any exterior foundation wall shall be observed.
   At no time shall the vertical water service pipe or the fixture supply piping be allowed to come into direct contact with cement or concrete.
   (e)   Meter Protection. The part of the water service that extends vertically from the excavated trench through the first floor (crawl space) shall be protected from freezing by enclosing the same with six-inch diameter conductor pipe. This conductor pipe shall be securely fastened to the floor joist in such a manner that the water service will be located in the center of the six-inch conductor pipe tube, which shall extend to the underside of the flooring. The space between the conductor pipe tube and the water service shall be filled with an approved insulation. The six-inch conductor pipe tube shall be installed by the plumber.
   (f)   Replacement. A permit shall be required to replace any water or sewer line.
(Ord. 2528. Passed 4-5-77.)
   (g)   Prohibitions. No water service shall be installed on or across adjoining lots. No water service shall be laid in the same ditch as the building sewer, except as provided for in division (d) of this section.
(Ord. 3048. Passed 9-2-80.)