826.12 WATER SUPPLY SYSTEM.
   (a)   A facility shall connect to and use a public water system.
   (b)   There shall be no cross connections between water systems that are safe for human consumption and those that are, or may become, unsafe for human consumption.
   (c)   Minimum water pressure available to each plumbing fixture shall exceed twenty pounds per square inch.
   (d)   The plumbing system shall supply an adequate amount of hot water at all times to meet the needs of each patient and the functioning of the various service areas.
   (e)   Hot water temperatures at fixture outlets shall be regulated to provide tempered water in the range of 110 to 125 degrees Fahrenheit.
(Ord. 1978-72. Passed 10-18-78.)