929.04 DEFINITIONS.
   (a)   “Approved” shall mean accepted by the Water Purveyor as meeting an applicable specification stated or cited in this regulation, or as suitable for the proposed purpose.
   (b)   “Auxiliary Water Supply” shall mean any water supply on or available to the premises other than the purveyor’s approved public potable water supply.
   (c)   “Backflow” shall mean the flow of water or other liquids, mixtures or substances, under positive or reduced pressure in the distribution pipes of a potable water supply from any source other than its intended source.
   (d)   “Backflow Preventer” shall mean a device or means designed to prevent backflow or back-siphonage. Most commonly categorized as air gap, reduced pressure principle device, double check valve assembly, pressure vacuum breaker, atmospheric vacuum breaker, hose bibb vacuum breaker, residential dual check, double check with intermediate atmospheric vent, and barometric loop.
      (1)   “Air Gap” shall mean a physical separation sufficient to prevent backflow between the free-flowing discharge end of the potable water system and any other system. Physically defined as a distance equal to twice the diameter of the supply side pipe diameter but never less than one (1) inch.
      (2)   “Atmospheric Vacuum Breaker” shall mean a device which prevents back- siphonage by creating an atmospheric vent when there is either a negative pressure or sub-atmospheric pressure in a water system.
      (3)   “Barometric Loop” shall mean a fabricated piping arrangement rising at least thirty-five (35) feet at its topmost point above the highest fixture it supplies. It is utilized in water supply systems to protect against back- siphonage.
      (4)   “Double Check Valve Assembly” shall mean an assembly of two (2) independently operating spring loaded check valves with tightly closing shutoff valves on each side of the check valves, and properly located test cocks for the testing of each check valve.
      (5)   “Double Check Valve with Intermediate Atmospheric Vent” shall mean a device having two (2) spring loaded check valves separated by an atmospheric vent chamber.
      (6)   “Hose Bibb Vacuum Breaker” shall mean a device which is permanently attached to a hose bibb and which acts as an atmospheric vacuum breaker.
      (7)   “Pressure Vacuum Breaker” shall mean a device containing one or two independently operated spring loaded check valves and an independently operated spring loaded air inlet valve located on the discharge side of the check or checks. The device includes tightly closing shut-off valves on each side of the check valves and properly located test cocks for the testing of the check valve(s).
      (8)   “Reduced Pressure Principle Backflow Preventer” shall mean an assembly consisting of two (2) independently operating approved check valves with an automatically operating differential relief valve located between the two (2) check valves, tightly closing shut-off valves on each side of the check valves plus properly located test cocks for the testing of the check valves and the relief valve.
      (9)   “Residential Dual Check” shall mean an assembly of two (2) spring loaded, independently operating check valves without tightly closing shut-off valves and test cocks. Generally employed immediately downstream of the water meter to act as a containment device.
   (e)   “Backpressure” shall mean a condition in which the owner’s system pressure is greater than the supplier’s system pressure.
   (f)   “Back-siphonage” shall mean the flow of water or other liquids, mixtures or substances into the distribution pipes of a potable water supply system from any source other than its intended source caused by the sudden reduction of pressure in the potable water supply system.
   (g)   “Containment” shall mean a method of backflow prevention which requires a backflow prevention device at the water service entrance.
   (h)   “Contaminant” shall mean a substance that will impair the quality of the water to a degree that it creates a serious health hazard to the public leading to poisoning or the spread of disease.
   (i)   “Cross-connection” shall mean any actual or potential connection between the public water supply and a source of contamination or pollution.
   (j)   “Fixture Isolation” shall mean a method of backflow prevention in which a backflow preventer is located to correct a cross connection at an in-plant location rather than at a water service entrance.
   (k)   “Owner” shall mean any person who has legal title to, or license to operate or reside in, a property upon which a cross-connection inspection is to be made or upon which a cross-connection is present.
   (l)   “Person” shall mean any individual, partnership, company, public or private corporation, political subdivision or agency of the State Department, agency or instrumentality or the United States or any other legal entity.
   (m)   “Pollutant” shall mean a foreign substance, which if permitted to get into the public water system, will degrade its quality so as to constitute a moderate hazard, or impair the usefulness or quality of the water to a degree which does not create an actual hazard to the public health, but which does adversely and unreasonably affect such water for domestic use.
   (n)   “Water Purveyor” shall mean the Municipal Water Department, Water Board, Public Service District or other administrative authority invested with the authority and responsibility for the implementation of a cross-connection control program and for the enforcement of the provisions of the this article.
   (o)   “Water Service Entrance” shall mean that point in th owner’s water system beyond the sanitary control of the Water Purveyor, generally considered to be the outlet end of the water meter and always before any unprotected branch.
   (p)   “West Virginia Bureau for Public Health” or “WVBPH” shall mean the State of West Virginia Bureau for Public Health.
(Ord. 369. Passed 5-16-05.)