Loading...
DEVELOPMENT REQUIREMENTS
(A) Uses requiring permits. Artificial obstructions, including alterations and substantial improvements specifically listed in division (C) below, may be allowed by permit within the floodway, provided the general requirements in division (B) below and the applicable requirements in division (C) below are met.
(Prior Code, § 15.52.350)
(B) General requirements. An application for a permit shall meet the following requirements:
(1) All projects shall be designed and constructed to ensure that they do not adversely affect the flood hazard on other properties and are reasonably safe from flooding;
(2) All projects shall assure that the carrying capacity of the floodway is not reduced. All projects in the floodway shall meet the following:
(a) Demonstrate that the project does not increase the base flood elevation by conducting an encroachment analysis certified by an engineer. A minimal or qualitative encroachment analysis may be accepted when the project or development does not require a structure, alteration of the floodway, involve fill, grading, excavation or storage of materials or equipment but is also certified by an engineer to not exceed the allowable encroachment to the base flood elevation; and
(b) The allowable encroachment to the base flood elevation is 0.00 feet, and no significant increase to the velocity or flow of the stream or watercourse unless approval of an alteration of the regulated flood hazard area pursuant to § 154.037 of this chapter and an approved FEMA Conditional Letter of Map Revision occurs before permit issuance.
(A.R.M. §§ 36.15.505, 36.15.604, 36.15.605(1)(b)) (44 C.F.R. §§ 60.3(a)(3) and (4), 65.12(a))
(3) An application for a floodplain permit must also demonstrate the following factors are considered and incorporated into the design of the use or artificial obstruction in the floodway:
(a) The danger to life and property due to backwater or diverted flow caused by the obstruction or use;
(A.R.M. § 36.15.216(2)(a)) (M.C.A. § 76-5-406(1))
(b) The danger that the obstruction or use may be swept downstream to the injury of others;
(A.R.M. § 36.15.216(2)(b)) (M.C.A. § 76-5-406(2)
(c) The availability of alternative locations;
(A.R.M. § 36.15.216(2)(c)) (M.C.A. § 76-5-406(3))
(d) Construct or alter the obstruction or use in such manner as to lessen the flooding danger;
(A.R.M. § 36.15.216(2)(d)) (M.C.A. § 76-5-406(4))
(e) The permanence of the obstruction or use and is reasonably safe from flooding;
(A.R.M. § 36.15.216(2)(e)) (M.C.A. § 76-5-406(5))
(f) The anticipated development in the foreseeable future of the area which may be affected by the obstruction or use;
(A.R.M. § 36.15.216(2)(f)) (M.C.A. § 76-5-406(6))
(g) Relevant and related permits for the project have been obtained;
(44 C.F.R. § 60.3(a)(2))
(h) Such other factors as are in harmony with the purposes of these regulations, the Floodplain and Floodway Management provisions found in Chapter 5 of Title 76, M.C.A. §§ 76-5-101 through 76-5-406, and the accompanying Administrative Rules of Montana; and
(A.R.M. § 36.15.216(2)(g)) (M.C.A. § 76-5-406(7))
(i) The safety of access to property in times of flooding for ordinary and emergency services.
(44 C.F.R. § 60.22(c)(7))
(Prior Code, § 15.52.360)
(C) Artificial obstructions. The following may be allowed as indicated:
(1) Mining of material requiring excavation from pits or pools provided, in addition to the requirements of division (B) above, that:
(a) A buffer strip of undisturbed land of sufficient width as determined by an engineer to prevent flood flows from channeling into the excavation is left between the edge of the channel and the edge of the excavation;
(A.R.M. § 36.15.602(1)(a))
(b) The excavation meets all applicable laws and regulations of other local and state agencies; and
(A.R.M. § 36.15.602(1)(b))
(c) Excavated material may be processed on site but is stockpiled outside the floodway.
(A.R.M. § 36.15.602(1)(c))
(2) Railroad, highway and street stream crossings, including other transportation related crossings provided, in addition to the requirements of division (B) above, that:
(a) Crossings are designed to offer minimal obstructions to the flood flow;
(A.R.M. § 36.15.602(2))
(b) Where failure or interruption of public transportation facilities would result in danger to public health or safety and where practicable and in consideration of Additional Guidance on 23 C.F.R. 650A, (formerly Federal-Aid Policy Guide Non-Regulatory Supplement NS 23 C.F.R., part
650A, September 30, 1992, Transmittal 5).
1. Bridge lower chords shall have freeboard to at least two feet above the base flood elevation to help pass ice flows, the base flood discharge and any debris associated with the discharge; and
2. Culverts shall be designed to pass the base flood discharge and maintain at least two feet freeboard on the crossing surface.
(c) Normal overflow channels, if possible are preserved to allow passage of sediments to prevent aggradations; and
(d) Mid stream supports for bridges, if necessary, have footings buried below the maximum scour depth.
(3) Limited filling for road and railroad embankments, including other transportation related embankments not associated with stream crossings and bridges provided, in addition to the requirements of division (B) above, that:
(a) The fill is suitable fill;
(b) Reasonable alternate transportation routes outside the floodway are not available; and
(A.R.M. § 36.15.602(3))
(c) The encroachment is located as far from the stream channel as possible.
(A.R.M. § 36.15.602(3))
(4) Buried or suspended utility transmission lines provided, in addition to the requirements of division (B) above, that:
(a) Suspended utility transmission lines are designed such that the lowest point of the suspended line is at least six feet higher than the base flood elevation;
(A.R.M. § 36.15.602(4))
(b) Towers and other appurtenant structures are designed and placed to withstand and offer minimal obstruction to flood flows;
(A.R.M. § 36.15.602(4))
(c) Alternatives such as alternative routes, directional drilling and aerial crossings are considered when technically feasible; and
(d) Utility transmission lines carrying toxic or flammable materials are buried to a depth of at least twice the calculated maximum scour depth determined by an engineer for the base flood.
(A.R.M. § 36.15.602(4))
(5) Storage of materials and equipment provided, in addition to the requirements of division (B) above, that:
(a) The material or equipment is not subject to major damage by flooding and is properly anchored to prevent flotation or downstream movement; or
(A.R.M. § 36.15.602(5)(a))
(b) The material or equipment is readily removable within the limited time available after flood warning. Storage of flammable, toxic or explosive materials shall not be permitted.
(A.R.M. § 36.15.602(5)(b))
(6) Domestic water supply wells provided, in addition to the requirements of division (B) above, that:
(a) They are driven or drilled wells located on ground higher than surrounding ground to assure positive drainage from the well;
(A.R.M. § 36.15.602(6))
(b) They require no other structures (e.g., a well house);
(A.R.M. § 36.15.602(6))
(c) Well casings are water tight to a distance of at least 25 feet below the ground surface and the well casing height is a minimum of two feet above the base flood elevation or capped with a water-tight seal and vented two feet above the base flood elevation;
(A.R.M. § 36.15.602(6))
(d) Water supply lines have a watertight seal where the lines enter the casing;
(A.R.M. § 36.15.602(6))
(e) All pumps and electrical lines and equipment are either of the submersible type or are adequately flood-proofed; and
(A.R.M. § 36.15.602(6))
(f) Check valves are installed on main water lines at wells and at all building entry locations.
(A.R.M. § 36.15.602(6)) (44 C.F.R. § 60.3(a)(5))
(7) Buried and sealed vaults for sewage disposal in campgrounds and recreational areas provided, in addition to the requirements of division (B) above, demonstrate approval by the state’s Department of Environmental Quality and local health and sanitation permits or approvals;
(A.R.M. § 36.15.602(7)) (44 C.F.R. § 60.3(a)(6))
(8) Public and private campgrounds provided, in addition to the requirements of division (B) above, that:
(a) Access roads require only limited fill and do not obstruct or divert flood waters;
(A.R.M. § 36.15.602(8))
(b) The project meets the accessory structures requirements in this section;
(c) No dwellings or permanent mobile homes are allowed;
(A.R.M. § 36.15.602(8))
(d) Recreational vehicles and travel trailers are ready for highway use with wheels intact, with only quick disconnect type utilities and securing devices, and have no permanently attached additions; and
(44 C.F.R. § 60.3(c)(14))
(e) There is no large-scale clearing of riparian vegetation within 50 feet of the mean annual high water mark.
(9) Structures accessory or appurtenant to permitted uses such as boat docks, loading and parking areas, marinas, sheds, emergency airstrips, permanent fences crossing channels that may impede or stop flows or debris, picnic shelters and tables and lavatories, that are incidental to a principal structure or use, provided in addition to the requirements of division (B) above, that:
(a) The structures are not intended for human habitation or supportive of human habitation;
(A.R.M. § 36.15.602(9))
(b) The structures will have low flood damage potential;
(A.R.M. § 36.15.602(9))
(c) The structures will, insofar as possible, be located on ground higher than the surrounding ground and as far from the channel as possible;
(A.R.M. § 36.15.602(9))
(d) The structures will be constructed and placed so as to offer a minimal obstruction to flood flows;
(A.R.M. § 36.15.602 (9))
(e) Only those wastewater disposal systems that are approved under health and sanitation regulations are allowed;
(f) Service facilities within these structures such as electrical, heating and plumbing are flood-proofed according to the requirements in § 154.071 of this chapter;
(A.R.M. § 36.15.602(9))
(g) The structures are firmly anchored to prevent flotation;
(A.R.M. § 36.15.602(9))
(h) The structures do not require fill and/or substantial excavation;
(i) The structures or use cannot be changed or altered without permit approval; and
(j) There is no clearing of riparian vegetation within 50 feet of the mean annual high water mark.
(10) Construction of or modifications to surface water diversions provided, in addition to the requirements of division (B) above, that the design is reviewed and approved by an engineer and includes:
(a) Measures to minimize potential erosion from a base flood; and
(A.R.M. § 36.15.603(3)(b))
(b) Designs and plans that demonstrate any permanent structure in the stream is designed to safely withstand up to the base flood considering the forces associated with hydrodynamic and hydrostatic pressures including flood depths, velocities, impact, ice buoyancy and uplift forces associated with the base flood.
(A.R.M. § 36.15.603(3)(c)) (44 C.F.R. § 60.3(a)(3), 60.3(d)(3))
(11) Flood control and stream bank stabilization measures provided, in addition to the requirements of division (B) above, that the design is reviewed and approved by an engineer and constructed to substantially resist or withstand the forces associated with hydrodynamic and hydrostatic pressures, including flood depths, velocities, impact, ice, buoyancy and uplift associated with the base flood. The design must also show compliance with the following applicable criteria:
(A.R.M. § 36.15.606) (44 C.F.R. § 60.3(a)(3), 60.3(d)(3))
(a) Levee and floodwall construction or alteration:
1. Must be designed and constructed with suitable fill and be designed to safely convey a base flood;
(A.R.M. § 36.15.606(1)(a))
2. Must be constructed at least three feet higher than the elevation of the base flood unless the levee or floodwall protects agricultural land only;
(A.R.M. § 36.15.606(2)(a))
3. Must meet state and federal levee engineering and construction standards and be publicly owned and maintained if it protects structures of more than one landowner; and
(A.R.M. § 36.15.505(1)(c)(ii) and (iii))
4. For any increase in the elevation of the base flood, an alteration of the regulated flood hazard area requires approvals pursuant to § 154.037 of this chapter.
(b) Stream bank stabilization, pier and abutment protection projects:
1. Must be designed and constructed using methods and materials that are the least environmentally damaging yet practicable, and should be designed to withstand a base flood once the project’s vegetative components are mature within a period of up to five years or other time as required by the Floodplain Administrator. Once vegetation is mature and established, it should not require substantial yearly maintenance after the initial period;
2. Materials for the project may be designed to erode over time, but not fail catastrophically and impact others. Erosion, sedimentation and transport of the materials may be designed to be at least similar in amount and rate of existing stable natural stream banks during the base flood;
3. Must not increase erosion upstream, downstream, across from or adjacent to the site in excess of the existing stable natural stream bank during the base flood; and
(A.R.M. § 36.15.606(1)(b))
4. Materials for the project may include, but are not limited to, riprap, root wads, brush mattresses, willow wattles, natural woody debris or combinations of analogous materials.
(c) Channelization projects where the excavation and/or construction of a channel is for the purpose of diverting the entire or a portion of the flow of a stream from its established course, the project must:
1. Not increase the magnitude, velocity or elevation of the base flood; and
2. Meet the requirements of this division (C)(11).
(A.R.M. §§ 36.15.101(7), 36.15.606(1)(c))
(d) Dams:
1. The design and construction shall be in accordance with the state’s Dam Safety Act and applicable safety standards; and
2. The project shall not increase flood hazards downstream either through operational procedures or improper hydrologic/hydraulic design.
(A.R.M. § 36.15.606(1)(d))
(12) Stream and bank restoration projects intended to reestablish the terrestrial and aquatic attributes of a natural stream and not for protection of a structure or development provided, in addition to the requirements of division (B) above, that:
(a) The project will not increase velocity or erosion upstream, downstream, across from or adjacent to the site;
(A.R.M. § 36.15.606(1)(b))
(b) Materials may include, but are not limited to, boulders, rock cobble, gravel, native stream bed materials, root wads, brush mattresses, willow wattles, natural woody debris or combinations of analogous materials and that reasonably replicates the bed and bank of the natural stream;
(c) Erosion, sedimentation and transport of the materials are not more than the amount and rate of existing natural stream banks during the base flood; and
(d) The project may be designed to allow vegetative materials to mature within a period up to five years or other time as required by the Floodplain Administrator. Once vegetation is mature and established, it should not require substantial yearly maintenance after the initial period.
(13) Existing residential and non-residential buildings in the floodway. Any alteration or substantial improvement to an existing building must meet the requirements of division (B) above and the applicable requirements in this section for residential or non-residential buildings.
(M.C.A. § 76-5-404(3)(b))
(Prior Code, § 15.52.370)
(Ord. 455, passed 11-23-2021)
(A) Uses requiring permits.
(1) All uses allowed by permit in the floodway shall also be allowed by permit within the flood fringe or regulated flood hazard area with no floodway. Such uses are subject to the requirements in § 154.070 of this chapter, with the exception of the encroachment limit of § 154.070(B)(2) of this chapter. Instead, such uses are subject to the encroachment limits of division (B)(1) below.
(2) Except for prohibited artificial obstructions in § 154.039(B) of this chapter, all other artificial obstructions, including new construction, substantial improvements, alterations to residential and non-residential structures, including manufactured homes, and related suitable fill or excavation shall be allowed by permit and are subject to the requirements in this section and general requirements of § 154.070(B) of this chapter, with the exception of the encroachment limit of § 154.070(B)(2) of this chapter.
(A.R.M. § 36.15.701(2))
(Prior Code, § 15.52.380)
(B) General requirements. An application for a floodplain permit must demonstrate or meet the following applicable requirements.
(1) Base flood elevation. Where necessary to meet the appropriate elevation requirement in these regulations, the base flood elevation(s) must be determined by an engineer and utilized in the design and layout of the project demonstrating the design and construction criteria herein are met. For regulated flood hazard areas that do not have computed and published base flood elevations in the adopted flood hazard study referenced in §§ 154.035 through 154.037 of this chapter, a base flood elevation must be determined or obtained from a reliable source, utilizing appropriate engineering methods and analyses.
(2) Flood damage. Structures must be constructed by methods and practices that minimize flood damage and structures must be reasonably safe from flooding.
(44 C.F.R. § 60.3(a), (a)(3)(iii))
(3) Surface drainage. Adequate surface drainage must be provided around structures.
(4) Materials. Structures must be constructed with materials resistant to flood damage.
(44 C.F.R. § 60.3(a), (a)(3)(ii))
(5) Artificial obstructions. Structures, excavation or fill must not be prohibited by any other statute, regulation, ordinance or resolution; and must be compatible with subdivision, zoning and any other land use regulations, if any.
(A.R.M. § 36.15.701(3)(a), (3)(b))
(6) Anchoring. All construction and substantial improvements must be designed and adequately anchored to prevent flotation, collapse or lateral movement of the structure resulting from hydrodynamic and hydrostatic loads, including the effects of buoyancy.
(44 C.F.R. § 60.3(a)(3))
(7) Certification. Certification by an engineer, architect, land surveyor or other qualified person must accompany the application where required including for an encroachment analysis, adequacy of structural elevations, base flood elevation determinations, flood-proofing, enclosure flood openings and design and construction to withstand the hydrodynamic forces and hydrostatic pressures of flood depths, velocities, impact, buoyancy, uplift forces associated with the base flood and surface drainage. A certification is not intended to constitute a warranty or guarantee of performance, expressed or implied.
(A.R.M. §§ 36.15.606(1), 36.15.702(2)(c), 36.15.801(3)(b)) (44 C.F.R. § 60.3(c)(3) and (4), 60.3(d)(3))
(8) Access. Structures must have safe access during times of flooding up to the base flood for ordinary and emergency services provided there are no reasonable alternate locations for structures.
(9) Encroachment analysis.
(a) All applications in the regulated flood hazard area without a floodway must be supported by an encroachment analysis of the proposed use, a thorough hydrologic and hydraulic analysis, except as provided in division (B)(9)(d) below, prepared by an engineer to demonstrate the effect of the structure on flood flows, velocities and the base flood elevation;
(A.R.M. § 36.15.604) (44 C.F.R. § 60.3(a)(3))
(b) The maximum allowable encroachment is certified to be at or less than one- half feet increase to the base flood elevation unless approval of an alteration of the regulated flood hazard area pursuant to §§ 154.035 through 154.037 of this chapter and an approved FEMA Conditional Letter of Map Revision occurs before permit issuance;
(A.R.M. §§ 36.15.505, 36.15.604) (44 C.F.R. § 60.3(c)(13))
(c) An encroachment analysis is not required for any development in the flood fringe where an accompanying floodway has been designated within the regulated flood hazard area; and
(d) Although all other development standards herein apply, a minimal or qualitative encroachment analysis may be accepted when the project or development does not require a structure, alteration of the floodplain, involve fill, grading, excavation or storage of materials or equipment and also is certified by an engineer to not exceed the allowable encroachment.
(10) Electrical systems flood-proofing. All electrical service materials, equipment and installation for uses in a regulated flood hazard area must be certified to meet the following requirements:
(a) All incoming power service equipment, including all metering equipment, control centers, transformers, distribution and lighting panels and all other stationary equipment, must be located at least two feet above the base flood elevation;
(A.R.M. § 36.15.901(1)(a))
(b) Portable and movable electrical equipment may be placed below the base flood elevation, provided that the equipment can be disconnected by a single plug and socket assembly of the submersible type;
(A.R.M. § 36.15.901(1)(b))
(c) The main power service lines must have automatically operated electrical disconnect equipment or manually operated electrical disconnect equipment located at an accessible remote location outside the regulated flood hazard area or two feet above the base flood elevation; and
(A.R.M. § 36.15.901(1)(c))
(d) All electrical wiring systems installed below the base flood elevation must be suitable for continuous submergence and may not contain fibrous components.
(A.R.M. § 36.15.901(1)(d))
(11) Heating and cooling systems flood proofing. Heating and cooling systems for uses in a regulated flood hazard area must be certified to meet the following requirements.
(a) Float-operated automatic control valves must be installed so that fuel supply is automatically shut off when flood waters reach the floor level where the heating and cooling systems are located.
(A.R.M. § 36.15.902(1)(a))
(b) Manually operated gate valves must be installed in gas supply lines. The gate valves must be operable from a location above the base flood elevation.
(A.R.M. § 36.15.902(1)(b))
(c) Electrical systems flood proofing must be met.
(A.R.M. § 36.15.902(1)(c))
(d) Furnaces and cooling units must be installed at least two feet above the base flood elevation and the ductwork installed above the base flood elevation.
(12) Plumbing systems flood-proofing. Plumbing systems for uses in the regulated flood hazard area must be certified to meet the following requirements.
(a) Sewer lines, except those to a buried and sealed vault, must have check valves installed to prevent sewage backup into permitted structures.
(A.R.M. § 36.15.903(1)(a))
(b) All toilets, stools, sinks, urinals, vaults and drains must be located so the lowest point of possible flood water entry is at least two feet above the base flood elevation.
(A.R.M. § 36.15.903(1)(b))
(13) Structural fill flood-proofing. Fill used to elevate structures, including, but not limited to, residential and non-residential buildings must be certified to meet the following requirements.
(a) The filled area must be at or above the base flood elevation and extend at least 15 feet beyond the structure in all directions.
(b) Fill material must be suitable fill, that is stable, compacted, well graded and pervious, not adversely affected by water and frost, devoid of trash or similar foreign matter, tree stumps or other organic material; and is fitting for the purpose of supporting the intended use and/or permanent structure.
(A.R.M. § 36.15.101(22))
(c) The fill must be compacted to minimize settlement and compacted to 95% of the maximum density. Compaction of earthen fill must be certified by an engineer.
(d) No portion of the fill is allowed within the floodway.
(e) The fill slope must not be steeper than one and one-half horizontal to one vertical unless substantiating data justifying a steeper slope is provided and adequate erosion protection is provided for fill slopes exposed to flood waters.
(14) Wet flood-proofing. Building designs with an enclosure below the lowest floor must be certified to meet the following.
(a) Materials used for walls and floors are resistant to flooding to an elevation two feet or more above the base flood elevation.
(A.R.M. § 36.15.702(2)(a))
(b) The enclosure must be designed to equalize hydrostatic forces on walls by allowing for entry and exit of flood waters. Opening designs must either be certified by an engineer or architect or meet or exceed the following:
1. Automatically allow entry and exit of flood waters through screens, louvers, valves and other coverings or devices;
2. Have two or more openings with a total net area of not less than one square inch for every one square foot of enclosed area below the lowest floor, except if the enclosure is partially subgrade, a minimum of two openings may be provided on a single wall; and
3. Have the bottom of all openings no higher than one foot above the higher of the exterior or interior adjacent grade or floor immediately below the openings.
(44 C.F.R. § 60.3(c)(5)) (NFIP Insurance Manual, Rev. May 2013)
(15) Dry flood-proofing. Building designs that do not allow internal flooding must be certified according to these regulations to meet the following:
(a) Building use must be for non-residential use only and does not include mixed residential and non-residential use;
(b) Be flood-proofed to an elevation no lower than two feet above the base flood elevation;
(c) Be constructed of impermeable membranes or materials for floors and walls and have water-tight enclosures for all windows, doors and other openings; and
(d) Be designed to withstand the hydrostatic pressures and hydrodynamic forces resulting from the base flood and the effects of buoyancy.
(A.R.M. § 36.15.702(2)(b)) (44 C.F.R. § 60.3(c)(3))
(16) Elevation of the lowest floor. Elevating the lowest floor may be by either suitable fill, foundation wall enclosure, stem walls, pilings, posts, piers, columns or other acceptable means;
(M.C.A. § 76-5-402(2)(b)) (44 C.F.R. § 60.3(b)(8), 60.3(c)(6))
(17) Crawl spaces. Crawl space foundation enclosures including subgrade crawlspace enclosures below the lowest floor must meet the wet flood proofing requirements and be designed so that the crawl space floor is at or above the base flood elevation. Crawl space foundations must have an inside dimension of not more than five feet from the ground to the top of the living floor level and a subgrade crawlspace must also have the interior ground surface no more than two feet below the exterior lowest adjacent ground surface on all sides. A subgrade foundation exceeding either dimension is a basement;
(18) Manufactured home anchors. For new placement, substantial improvement or replacement of manufactured homes for residential or non-residential use including additions, the chassis must be secure and must resist flotation, collapse or lateral movement by anchoring with anchoring components capable of carrying a force of 4,800 pounds and as follows.
(a) For manufactured homes less than 50 feet long, over-the-top ties to ground anchors are required at each of the four corners of the home, with two additional ties per side at intermediate locations.
(b) For manufactured homes more than 50 feet long, frame ties to ground anchors are required at each corner of the home with five additional ties per side at intermediate points.
(44 C.F.R. § 60.3(b)(8), 60.3(c)(6))
(19) Access. Access for emergency vehicles is provided. For manufactured homes, access for a manufactured home hauler is also provided.
(Prior Code, § 15.52.390)
(C) Residential building, exceptions and additional requirements. New construction, alterations and substantial improvements of residential dwellings, manufactured homes, including replacement of manufactured homes, must be constructed such that:
(1) Elevation of the lowest floor. The lowest floor of the building, including an attached garage or basement, must be two feet or more above the base flood elevation;
(A.R.M. § 36.15.701(3))
(2) Enclosure. Enclosures of elevated buildings cannot be dry flood-proofed. Use for an enclosure is limited to facilitating building component access. The enclosure including a crawlspace must be wet flood-proofed and the enclosure floor must be at or above the base flood elevation. An attached garage floor must be two or more feet above the base flood elevation; and
(3) Recreation vehicles. Recreational vehicles on site for more than 180 days or not ready for highway use must meet the requirements for manufactured homes for residential use.
(Prior Code, § 15.52.400)
(D) Non-residential building, exceptions and additional requirements. New construction, alterations and substantial improvements of non-residential including agricultural, commercial and industrial buildings and residential and non-residential accessory buildings must be constructed such that:
(1) Elevation of the lowest floor. The lowest floor of the building must be elevated two feet above the base flood elevation or adequately dry flood-proofed according to this chapter. The lowest floor may be wet proofed; provided, the use is limited to only parking, loading and storage of equipment or materials not appreciably affected by flood water;
(A.R.M. § 36.15.702(2)) (44 C.F.R. § 60.3(c)(3), (c)(3)(ii), (c)(4))
(2) Enclosure. Enclosures below the lowest floor on elevated buildings must be wet flood-proofed and the use must be limited to parking, access or storage or must be adequately dry flood- proofed according to this section;
(3) Manufactured homes. Manufactured homes proposed for use as non-residential buildings cannot be dry flood-proofed; and
(4) Agricultural structures. Agricultural structures not intended to be insurable, used solely for agricultural purposes, having low flood damage potential, used exclusively in connection with the production, harvesting, storage, drying or raising of agricultural commodities, including raising of livestock, and not intended for human habitation are exempt from the elevation requirement, dry or wet flood-proofing, but shall:
(a) Be located on higher ground and as far from the channel as possible;
(b) Offer minimal obstruction to flood flows;
(c) Be adequately anchored to prevent flotation or collapse;
(d) Where electrical, heating and plumbing systems are installed, meet the flood proofing requirements in divisions (B)(1)(j), (B)(1)(k) and (B)(1)(l) above; and
(e) Meet the elevation or dry flood-proofing requirements if the structure is an animal confinement facility.
(A.R.M. §§ 36.15.602(9), 36.15.701(3)(e), 36.15.702(2))
(Prior Code, § 15.52.410)
(Ord. 455, passed 11-23-2021)
Loading...