951.05 TESTING; REGISTER LIMITS.
   Upon examination and test of meters, after they have been in service a reasonable length of time, they must register within the following percentages of the actual amount of water passed through them:
 
 
Meter Size (Inches)
Register Limits
5/8
Within 2% plus or minus on all streams from 20 gallons per minute down to 1 gallon per minute, and within 10% minus on ½ gallon per minute
3/4
Within 2% plus or minus on all streams from 35 gallons per minute down to 1 gallon per minute, and within 10% minus on ½ gallon per minute
1
Within 2% plus or minus on all streams from 60 gallons per minute down to 3 gallons per minute, and within 10% minus on 4 gallons per minute
3
Within 2% plus or minus on all streams from 320 gallons per minute down to 15 gallons per minute, and within 10% minus on 4 gallons per minute
4
Within 2% plus or minus on all streams from 560 gallons per minute down to 28 gallons per minute, and within 10% minus on 7 gallons per minute
6
Within 2% plus or minus on all streams from 960 gallons per minute down to 48 gallons per minute, and within 10% minus on 12 gallons per minute
(Ord. 1435. Passed 12-18-61.)