(a) The owners of any structures (except one and two-family dwellings, private residential garages) or any installation deemed hazardous by the Director Prevention Bureau, any part of which are 300 feet or more, as measured in Fire Department line of travel, from an existing fire hydrant, shall be required to provide fire hydrants and supply lines for fire protection.
(b) The requirements for each hydrant and supply line shall be determined by the Fire Department, and Municipal Water Department. Plans for installation shall be submitted to the Fire Department and the Municipal Water Department for their approval before installation.
(c) The following general provisions shall apply:
(1) No hydrant supply line shall be less than six inches diameter.
(2) In some cases, supply lines may have to be looped.
(3) All cost for installation of mains, hydrants, and appurtenances shall be the responsibility of the owner.
(4) All materials and installations shall be approved by, and conform to the City Fire Department, and Municipal Water Department standards and requirements.
(5) Normal hydrant maintenance and inspection shall be done by the owner.
(6) Owners of property on which there are existing fire hydrants shall be subject to all the requirements of this section.
(Ord. 167-96. Passed 9-16-96.)