911.526 ACCURACY OF METERS.
   (a)   New meters installed by the Division of Water shall meet the following accuracy specifications:
Positive Displacement Meters
 

Size
Rate of
Flow GPM
Accuracy Limits
Rate of Flow GPM
Accuracy Limits
Rate of
Flow GPM
Accuracy Limits
5/8"
1 - 20
99 - 101
1/4
95% or better
1/8
90% or better
3/4"
2 - 34
99 - 101
1/4
95% or better
1"
3 - 53
99 - 101
3/4
95% or better
Compound Meters
 

Size
Rate of
Flow GPM
Accuracy Limits
Rate of Flow GPM
Accuracy Limits
2"
2 - 160
98 - 102
1/2
95% or better
3"
4 - 315
98 - 102
1
95% or better
4"
6 - 500
98 - 102
1 1/2
95% or better
6"
10 - 1000
98 - 102
3
95% or better
8"
16 - 1600
98 - 102
4
95% or better
10"
32 - 2300
98 - 102
8
95% or better
At the cross-over point, accuracy of 96% to 104% is required.
   (b)   The accuracy of repaired meters shall be as follows:
Positive Displacement Meters
 

Size
Rate of
Flow GPM

Accuracy Limits
Rate of
Flow GPM

Accuracy Limits
5/8"
1 - 20
98 - 102
1/4
90% or better
3/4"
2 - 34
98- 102
1/4
90% or better
1"
3 - 53
98 - 102
3/4
90% or better
Compound Meters
 

Size
Rate of
Flow GPM
Accuracy Limits
Rate of
Flow GPM

Accuracy Limits
2"
2 - 160
97 - 103
1/2
90% or better
3"
4 - 315
97 - 103
1
90% or better
4"
6 - 500
97 - 103
1 1/2
90% or better
6"
10 - 1000
97 - 103
3
90% or better
8"
16 - 1600
97 - 103
4
90% or better
10"
32 - 2300
97 - 103
8
90% or better
(Ord. 167-96. Passed 9-16-96.)