§ 50.62 INSPECTION AND MAINTENANCE.
   (A)   It shall be the duty of the consumer at any premises on which backflow prevention devices required by these regulations are installed to have inspections, tests, maintenance and repairs made in accordance with the following schedule or more often where inspections indicate a need or are specified in manufacturer's instructions.
      (1)   Fixed proper air gap separations shall be inspected at the time of installation and at least annually thereafter.
      (2)   Double check valve assemblies shall be inspected and tested for tightness at time of installation and at least annually thereafter, and required service performed within 15 days.
      (3)   Reduced pressure principle backflow prevention devices shall be tested at least annually or more frequently if recommended by the manufacturer, and required service performed within five days.
   (B)   Testing shall be performed by a person who has been approved by the Agency as competent to service the device. Proof of approval shall be in writing.
   (C)   Each device shall have a tag attached listing the date of most recent test or visual inspection, name of tester and type and date of repairs.
   (D)   A maintenance log shall be maintained and include:
      (1)   Date of each test or visual inspection.
      (2)   Name and approval number of person performing the test or visual inspection;
      (3)   Test results;
      (4)   Repairs of servicing required;
      (5)   Repairs and date completed; and
      (6)   Servicing performed and date completed.
   (E)   Whenever backflow prevention devices required by these regulations are found to be defective, they shall be repaired or replaced at the expense of the consumer without delay.
   (F)   Backflow prevention devices shall not be bypassed, made inoperative, removed or otherwise made ineffective without specific authorization by the City Administrator.
(Ord. 99-227, passed 8-25-99)