§ 94.092  HYDRANT SPECIFICATIONS.
   Whenever the provisions of this chapter require the installation of a fire hydrant, whether on public or private property, the hydrant shall meet the following specifications.
   (A)   It (hydrant) must meet all city utility specifications.
   (B)   It shall be constructed with 2 two and one-half inch hose nozzles.
   (C)   It shall be equipped with 1 five-inch Storz connection.
   (D)   It shall be constructed to be opened by turning clockwise a national standard pentagon-operating nut.
   (E)   All privately owned hydrants shall be painted red with top color indicating the water main size, i.e.:
 
Red
4 inch main
Orange
6 inch main
White
8 inch main
Green
10 inch main
Blue
12 inch and above main
 
   (F)   No private citizen will be allowed to otherwise paint or alter a hydrant in any way and hydrants must be kept clear from obstructions of any kind for a distance of three feet.
(Ord. 2009-10, passed 11-30-2009)