§ 150.297 ADDITIONAL SPECIAL RULES.
   The following additional special rules and regulations are hereby adopted as part of the Lake Forest Electrical Code of 1992.
   (A)   All electrical wiring shall be in intermediate metallic conduit, rigid conduit, electrical metallic tubing as specified in Articles 345, 346, 348 of the National Electrical Code, except that other types of conduit or wiring protection may be permitted by the Chief Electrical Inspector or his or her authorized designee.
   (B)   Conduit on or below grade within a structure shall be galvanized rigid metal conduit. All exterior conduit shall be rigid, (steel or aluminum) or intermediate metallic.
   (C)   (1)   Circuits wired with AWG #14 wire shall be limited to eight outlets or receptacles for general lighting connected to a single circuit.
      (2)   Circuits wired with AWG #12 wire shall be limited to ten outlets or receptacles for general lighting connected to a single circuit.
   (D)   Cooling/heating equipment shall be provided with a disconnect on or adjacent to the equipment and an approved convenience receptacle shall be provided adjacent to such equipment.
   (E)   All floor receptacles shall be of an approved type.
   (F)   When a question arises as to a method or material used, the ruling of the Chief Electrical Inspector or his or her authorized designee shall govern.
(Prior Code, § 9-152) (Ord. 94-11B, passed 4-21-1994; Ord. 04-12, passed 1-15-2004)