§ 150.296 AMENDMENTS.
   Said National Electrical Code is hereby amended as follows.
   (A)   Section 110-5, “conductor” is amended to read as follows:
      Conductors normally used to carry current shall be of copper. Where the conductor material is not specified, the sizes given in this code shall apply to copper conductors.
   (B)   Section 110-16 is amended to read as follows:
      (1)   Working clearances. Except as elsewhere required or permitted in this code, the dimension of the working space in the direction of access to live parts operating at 600 volts nominal, or less and likely to require examination, adjustment, servicing or maintenance shall not be less than indicated in Table 110-16(1). The work space shall not be less than 36 inches wide on either side of the electric equipment. Distances shall be measured from the enclosure front (See the typical drawing in § 150.366. May be used to graphically interpret this requirement.)
 
Table 110-16(1). Working Clearances
Voltage to Ground
Minimum Clear Distance (Feet) Condition:
1
2
3
0—150
4
4
4
151—600
4
4-1/2
5
 
      (2)   Access and entrance to working space. At least one entrance of sufficient area shall be provided to give access to the working space about electric equipment. For switchboards and control panels rated 1200 amperes or more and over six feet wide, there shall be one entrance not less than 36 inches wide at each end.
      (3)   Front working space. In all cases where there are live parts normally exposed on the front of switchboard or motor control centers, the working space in front of such equipment shall not be less than four feet. (See the typical drawing in § 150.366. May be used to graphically interpret this requirement.)
      (4)   Illumination. Illumination shall be provided for all working spaces about service equipment, switchboards, panel boards or motor control centers installed indoors. (See the typical drawing in § 150.366. May be used to graphically interpret this requirement.) Exception to (e) in the National Electric Code is hereby deleted.
      (5)   Headroom. The minimum headroom of working spaces about service equipment, switchboards, panel boards or motor control centers shall be six feet six inches. (See the typical drawing in § 150.366. May be used to graphically interpret this requirement.)
   (C)   Section 210-8(a) Dwelling units is amended to read as follows:
      (a)   The provisions of this subchapter shall apply to all new construction and/or remodeling of commercial, public, institutional buildings and dwelling units.
   (D)   Section 210-8, paragraph (a) (5) is added and is amended to read as follows:
      (a)   (5)   All receptacles installed within six feet of any sink or wet location shall be GFCI protected.
   (E)   Section 210-8 is amended to read as follows;
      (a)   (7)   GFCl protected receptacles with slave capability shall not be permitted to connect to downstream receptacles or outlets other than those which are installed in the immediate area where the lead GFCl receptacle is located.
   (F)   Section 210-52 Dwelling unit receptacle outlets is amended to read as follows:
      (1)   General provisions. In every kitchen, family room, dining room, living room, parlor, library, den, sun room, bedroom, recreation room, screened porch or breezeway or similar room or area of dwelling units, receptacle outlets shall be installed so that no point along the floor line in any wall space is more than six feet (1.83 m), measured horizontally, from an outlet in that space, including any wall space two feet (610 mm) or more in width and the wall space occupied by fixed panels in exterior walls, but excluding sliding panels in exterior walls. The wall space afforded by fixed room dividers, such as freestanding bar-type counters, shall be included in the six foot (1.83 m) measurement.
      As used in this section a “wall space” shall be considered a wall unbroken along the floor line by doorways, fireplaces and similar openings. Each wall space two or more feet (610 mm or more) wide shall be treated individually and separately from other wall spaces within the room. A wall space shall be permitted to include two or more walls of a room (around corners) where unbroken at the floor line.
      (FPN): The purpose of this requirement is to minimize the use of cords across doorways, fireplaces and similar openings.
      Receptacle outlets shall, insofar as practicable, be spaced equal distances apart. Receptacle outlets in floors shall not be counted as part of the required number of receptacle outlets unless located close to the wall.
      The receptacle outlets required by this section shall be in addition to any receptacle that is part of any lighting fixture or appliance, located within cabinets or cupboards, or located over five and one-half feet (1.68 m) above the floor.
      Exception: Permanently installed electric baseboard heaters equipped with factory-installed receptacle outlets or outlets provided as separate assembly by the manufacturer shall be permitted as the required outlet or outlets for the wall space utilized by such permanently installed heaters. Such receptacle outlets shall not be connected to the heater circuits.
      (FPN): Listed baseboard heaters include instructions which may-not permit their installation below receptacle outlets.
   (G)   Section 225-6(b) is amended to read as follows:
      1.   Festoon Lighting. Not permitted.
   (H)   Section 225-13 Festoon supports is amended to read as follows:
      1.   Festoon Supports. Not permitted.
   (I)   Section 230-42(b) Ungrounded Conductors, size and rating is amended to read as follows:
      (1)   Ungrounded conductors shall not be smaller than:
         a.   200-ampere, three wire, for a new single-family dwelling; or
         b.   100-ampere, three wire, for an existing single-family dwelling; or
         c.   60 ampere for other loads, by special permission of the Chief Electrical Inspector or his or her authorized designee.
      Exception No. 1: For loads consisting of not more than two 2-wire branch circuits, No. 6 copper.
      Exception No. 2: By special permission for loads limited by demand or by the source of supply, No. 6 copper.
   (J)   Section 230-43 wiring methods for 600 volts, nominal or less is amended to read as follows:
      Wiring methods for 600 volts or less. Service entrance conductors shall be installed in accordance with the applicable requirements of this code covering the type of wiring method used and limited to the following methods:
      (1)   Rigid metal conduit; or
      (2)   Intermediate metal conduit; or
      (3)   For other methods by special permission of the Chief Electrical Inspector or his or her authorized designee.
   (K)   Section 230-50 protection of open conductors and cables against damage above ground is amended to read as follows:
      Service-entrance cables. Service-entrance cables shall be protected in any of the following ways:
      (1)   By rigid metal conduit; or
      (2)   By intermediate metal conduit; or
      (3)   For other methods by special permission of the Chief Electrical Inspector or his or her authorized designee.
   (L)   Section 230-72, Grouping of disconnects, is amended to read as follows:
      (a)   General. The two to six disconnects as permitted in § 230-71 shall be grouped. Each disconnect shall be marked to indicate the load served.
         Exception: One of the two to six service disconnecting means permitted in § 230-71, when used only for a water pump also intended to provide fire protection, shall be permitted to be located remote from the other disconnecting means.
      (b)   Additional service disconnecting means. The one or more additional service disconnecting means for fire pumps or for emergency, legally required standby, or optional standby services permitted by § 230-2 shall be installed sufficiently remote from the one to six service disconnecting means for normal service to minimize the possibility of simultaneous interruption of supply.
      (FPN): See § 700-12(d) and (e) for emergency system services.
      (c)   Access to occupants. In a multiple-occupancy building, each occupant shall have access to the occupant’s service disconnecting means.
      Exception: In a multiple-occupancy building where electric service and electrical maintenance are provided by the building management and where these are under continuous building management supervision, the service disconnecting means supplying more than one occupancy shall be permitted to be accessible to authorized management personnel only.
      (d)   A shunt trip service disconnect shall be provided on the exterior of every building, except one and two family dwellings.
   (M)   Section 230-84 More than one building or other structure is amended to read as follows:
      (b)   Suitable for service equipment. The disconnection means specified in (a) above shall be suitable for use as service equipment.
      Exception: deleted.
   (N)   Section 250-92 is amended to read as follows:
      (a)   Grounding electrode conductor. A grounding electrode conductor shall be in rigid metal conduit, intermediate metal conduit or electrical metallic tubing.
      Metal enclosures for grounding conductors shall be electrically continuous from the point of attachment to cabinets or equipment to the grounding electrode, and shall be securely fastened to the ground clamp or fitting. Where intermediate metal conduit is used for protection for a grounding conductor, the installation shall comply with the requirements of Article 345. Where rigid metal conduit is used as protection for a grounding conductor, the installation shall comply with the requirements of Article 346. Where electrical metallic tubing is used, the installation shall comply with the requirements of Article 348.
      Aluminum or copper-clad aluminum grounding conductors shall not be used.
   (O)   Reserved.
   (P)   Section 350-2 is amended to read as follows:
      Uses not permitted. Flexible metal conduit shall not be used as follows:
      (1)   In wet locations.
      (2)   In hoistways, other than provided in § 620-21.
      (3)   In storage-battery rooms.
      (4)   In any hazardous (classified) location other than permitted in §§ 501-4(b), 504-20.
      (5)   Where rubber-covered conductors are exposed to oil, gasoline or other materials having a deteriorating effect on rubber.
      (6)   Underground or embedded in poured concrete or aggregate.
   (Q)   Section 410-8(d) Location, is amended to read as follows:
      (d)   Light fixtures shall be installed in all closets as follows:
         (1)   On the wall above the closet door, provided the clearance between the fixture and a storage area where combustible material may be stored within the closet is not less than 18 inches.
         (2)   On the ceiling over an area which is unobstructed to the floor, containing an 18 inch clearance horizontally between the fixture and a storage area where combustible material may be stored within the closet.
         (3)   A flush recessed fixture equipped with a solid lens shall be considered outside the closet area.
         (4)   If a pull chain fixture is used, the pull chain shall be within 18 inches of the entrance door. Pendants shall not be installed in clothes closets.
   (R)   Sec. 680.41, Indoor installations is amended to read as follows:
      A spa, hot tub, bath tub or shower installed indoors, shall conform to the requirements of this part, and shall be connected by wiring methods of Chapter 3.
(Prior Code, § 9-151) (Ord. 94-11B, passed 4-21-1994; Ord. 04-12, passed 1-15-2004)