In addition to the standards contained in the rules, regulations, and codes, heretofore established, the following standards shall apply to all work subject to the provisions of this subchapter:
(A) Flexible metal conduit: Flexible metal conduit shall not be exposed to weather, wet locations, or refrigerated areas unless it be of the sealed-type or other non-corroding type raceway.
(B) Services. The minimum electrical service on new habitable buildings or in retrofit of an existing service shall be 100 amperes, 18 circuit capacity breaker type panel. A 200 amp service shall be no less than 32 circuit capacity.
(C) Grounding electrode conductor. The minimum size grounding electrode conductor shall be #4 bare solid copper or equivalent.
(D) Devices requiring maintenance. Service entrance equipment, distribution equipment, panel boards, motor controllers, or other electrical equipment devices, and the like, requiring maintenance shall be provided with adequate illumination.