(A) The connection between the building sewer and the municipal sewer shall be made at the “Y” branch, provided there is one.
(B) If no “Y” branch was left in the municipal sewer for the building sewer and the municipal sewer is not over 12 inches in diameter, a “Y” branch shall be installed in the municipal sewer at the desired location by the owner of the building sewer.
(C) Where the municipal sewer is over 12 inches in diameter and where no “Y” branch was left for the building sewer, a hole may be cut in the municipal sewer large enough to receive the end of the building sewer and the connection made so that the building sewer enters the municipal sewer at an angle of about 45 degrees. A 45-degree “L” may be used to make this connection. In no case shall the spigot end extend past the inside surface of the municipal sewer.
(D) A smooth joint shall be made and the connection made secure and watertight by encasing with concrete.
(Ord. 6619, passed 1-28-13)