1389.01 MINIMUM REQUIREMENTS.
   Where natural light and ventilation in an occupied room or space is not provided, artificial light and mechanical ventilation may be substituted, provided the minimum requirements listed in Table 1389A are met.
Table 1389A Minimum Requirements
 
TYPE OF ROOM OR AREA
ARTIFICIAL LIGHT
MECHANICAL VENTILATION
(AIR CHANGED PER HOUR)
(CU. FT.)
Bathrooms
5 foot candles on floor area at plumbing fixtures
8
Lavatories containing water closets
5 foot candles on floor area at plumbing fixtures
6
Kitchens
Natural light required
15
Stairs
1 foot candle on tread surfaces
2
All other habitable rooms
Natural light required
2
 
(Ord. 1992-101. Passed 1-14-92.)