9-2-2: AMENDMENTS, REVISIONS, AND CHANGES:
The following sections of the IBC are hereby amended, revised and changed as follows:
   105.2 Work Exempt From Permit: Delete exceptions nos. 1, 2, 3, 4, 5, 6, 8, 9, 10, 12.
   105.3.2 and 105.5 Time Limitations Of Applications: Change section as follows:
      "Building official is authorized to grant one extension of not more than 30 days."
   903.2 Additional Requirements: Change section as follows:
   A.   Applicability: In addition to the foregoing requirements, fire suppression systems shall be installed and maintained in full operating condition, by the building owner, as specified in this code, throughout the entire building or structure described in subsection B.
      1.   For all new construction.
      2.   At any time the occupancy use of the building is changed.
      3.   When the cost of the remodeling, or reconstruction exceeds twenty-five percent (25) of the value of the building or structure. If there is a disagreement, the value shall be determined by the average value of two (2) appraisals, one provided by the village and the second provided by the applicant.
      4.   At any time the height of the building or structure is enlarged.
      5.   At any time the floor area of a building or structure is enlarged in excess of five hundred (500) square feet.
   B.   Where Required:
      1.   In any buildings or structures or portions thereof of use groups A-1, A-2, A-3, and A-4.
      2.   In all buildings or structures or portions thereof of use group B when more than two thousand five hundred (2,500) square feet per floor in area or fire area or when more than three (3) stories in height.
      3.   In all buildings or structures or portions thereof of use group E when more than two thousand five hundred (2,500) square feet per floor in area or fire area or when more than three (3) stories in height.
      4.   In all buildings or structures or portions thereof of use group F-1 when more than two thousand five hundred (2,500) square feet per floor.
      5.   In all buildings or structures or portions thereof of use group H.
      6.   In all buildings or structures or portions thereof of use group I-1, I-2, and I-3.
      7.   In all buildings or structures or portions thereof of use group M, S-1, and U when more than two thousand five hundred (2,500) square feet per floor in area or more than three (3) stories in height.
   903.2.2 Group E: Delete: Exception.
   903.4 Sprinkler System Monitoring And Alarms: Delete: Exception 1 - 7.
   907 Fire Alarm And Detection Systems:
      907 Additional Requirements: Add: 907.2 Additional Requirements.
   907.2 Where Required: In addition to the foregoing requirements an automatic fire detection system shall be installed by the building owner, maintained in full operating condition by the building owner, and tied by the building owner directly to the Hinsdale fire department communications center in the locations described in A, B, and C.
   A.   New Construction: An automatic fire detection system complying with NFPA 72, 2002 edition, in all new buildings or structures, or new portions of buildings or structures, of use groups A-1, A-2, A-3, A-4, A-5, B; E, I-1, I-2, I-3, and M; and in all buildings of use groups R. All new fire alarm systems shall use wireless radio transmission technology approved by the Hinsdale fire department to meet the direct connect requirement.
   B.   Existing Structures: An automatic fire detection system complying with NFPA 72, 2002 edition, or an automatic fire suppression system complying with NFPA 13, 2002 edition:
      1.   In each existing building and structure in use groups A-1, A-2, A-3, A-4, and A-5; and
      2.   In each existing building and structure in use groups E, I-1, I-2, and I-3; and
      3.   In each existing building and structure in use groups B and M when such building or structure is located in the area bounded by the Burlington RR, Second Street, Grant Street, and Garfield Street; and
      4.   In each existing building or structure in use groups B and M when such building or structure exceeds 10,000 square feet of gross floor area (as defined in the life safety code, 2003 edition); and
      5.   In each existing building or structure in use group R.
   C.   Sprinklered Building Exception: All new and existing buildings that are equipped throughout with an approved automatic fire suppression system complying with NFPA 13, 2002 edition, shall not be required to have an automatic fire detection system, but shall be equipped with a manual fire protective signaling system complying with NFPA 72, 2002 edition.
   907.20 Occupancy Permits: Add:
      907.20 Occupancy Permits: No certificate of occupancy shall be issued for new construction or for renovated or rebuilt premises until the provisions of section 907.2 have been satisfied.
   907.21 New Automatic Detection Systems: Add:
      907.21 New Automatic Detection Systems: All new automatic detection systems in every building shall be tied directly to the Hinsdale communications center.
   907.22 New Fire Alarm Systems: Add:
      907.22 New Fire Alarm Systems: All new fire alarm systems shall be fully addressable.
   907.23 Conflicts: Add:
      907.23 Conflicts: In the event of any conflict between the provisions of section 907 and the provisions of the life safety code, 2003 edition, the more stringent requirement shall be applied.
   1507.8 Wood Shingles: Delete requirements 3 and 4.
   1507.9 Wood Shakes: Delete requirements 3 and 4.
   3002.2 Elevator Car To Accommodate Ambulance Stretcher: Change section to read as follows:
      Where elevators are provided in buildings three or more stories above grade plane or three or more stories below grade plane, at least one elevator shall be provided for fire department emergency access to all floors. The elevator car shall be of such size and arrangement to accommodate a 24 inch by 84 inch ambulance stretcher in the horizontal, open position and shall be identified by the international symbol for emergency medical services (Star of Life). The symbol shall be not less than three inches high and shall be placed inside on both sides of the hoistway door frame.
(Ord. O2008-46, 8-12-2008)