Skip to code content (skip section selection)
Compare to:
5-2-3: AMENDMENTS TO THE INTERNATIONAL BUILDING CODE:
The International Building Code, adopted by reference pursuant to this Chapter 1 is amended as set forth in this Section 4-1-7. Subsequent section numbers used in this Section shall refer to the like numbered sections of the International Building Code.
   101 Delete "[NAME OF JURISDICTION]" and replace with "The Village of Hampshire, Illinois."
   101.2.3 Delete the term "International Plumbing Code" and replace with "Illinois Plumbing License Law, 225 ILCS 320/0.01 et seq., and the regulations adopted thereunder ("Illinois Plumbing Law"), as adopted by the Village and amended pursuant to Chapter 6 of this Title. Insert after the first sentence: "Every reference to the ICC International Plumbing Code in the International Building Code shall mean and refer to the Illinois Plumbing Law." Delete the entire last sentence of the section without substitution.
   101 4.8 Add the following new Section 101.4.8:
   “101.4.8 Electrical. The provisions of the 2017 Edition of the National Electric Code (NFPA 70) as adopted by the Village and amended pursuant to Article 7 of this Title ("Electric Code"), shall apply to the installation of electrical systems, including alterations, repairs, replacement, equipment, appliances, fixtures, fittings and appurtenances thereto. Every reference to the ICC Electrical Code in the International Building Code shall mean and refer to the National Electric Code.”
   101 4.9 Add the following new Section 101.4.9:
   “101.4.9 International Building Code Commentary. The narratives in the commentary to International Building Code shall apply, as a supplement, to the International Building Code.”
   101.3 Building: Delete numbers 1 and 2, then renumber to read:
   “1.   Oil derricks.
   2.   Retaining walls that are not over 4 feet (1219 mm) in height measured from the bottom of the footing to the top of the wall, unless supporting a surcharge or impounding class I, II or IIIA liquids.
   3.   Water tanks supported directly on grade if the capacity does not exceed 5,000 gallons (18,925 I) and the ratio of height to diameter or width does not exceed 2:1.
   4.   Sidewalks and driveways not more than thirty (30) inches (762 mm) above adjacent grade, and not over any basement or story below and are not part of an accessible route and not in the parkway area.
   5.   Painting, papering, tiling, carpeting, cabinets, counter tops, and similar finish work.
   6.   Temporary motion picture, television and theater stage sets and scenery.
   7.   Prefabricated swimming pools accessory to a group R-3 occupancy that are capable of holding less than 24 inches (610 mm) of water and/or inflatable, temporary swimming pools of any water depth, do not exceed 5,000 gallons (18,925 I), and are installed entirely above ground.
   8.   Shade cloth structures constructed for nursery or agricultural purposes, not including service systems.
   9.   Swings and other playground equipment accessory to detached one- and two-family dwellings.
   10.   Window awnings supported by an exterior wall that do not project more than 54 inches (1372 mm) from the exterior wall and do not require additional support of group R-3 and U occupancies.
   11.   Nonfixed and moveable fixtures, cases, racks, counters, and partitions not over 5 feet 9 inches (1753 mm) in height."
   (Rest of section remains the same.)
   Add new Section 105.8 as follows:
   "105.8 Bond. For any building permit to be issued for construction activities at a location where public improvements at or adjacent to said location, including but not limited to streets, paving, curbs and gutters, sidewalks, driveway aprons, trees, landscaping, manholes, fire hydrants, auxiliary valves, buffalo boxes, storm and sanitary sewers, sump pump connections, street lights and wiring, and/or final grading, have previously been constructed and/or installed, and have been certified as complete and/or have been accepted by the village, the application for issuance of a building permit shall be accompanied by a bond, in an amount set by the village administrator, subject to any schedule of amounts that may be established from time to time by the board of trustees, to secure against loss occasioned by damage to any of said public improvements. Said bond, or the balance remaining after application of said bond to any such damages, may be released to the applicant upon issuance by the village of a certificate of occupancy for the new building."
   Delete Section 109.4 and replace as follows:
   "109.4 Work Commencing Before Permit Issuance. Any person who commences any work on a building, structure, electrical, gas, mechanical or plumbing system before obtaining the necessary permits shall be subject to one hundred (100) percent of the usual permit fee in addition to the required permit fee. In the event that any building is undertaken without compliance with the above referenced fee schedule after thirty (30) days when notified of noncompliance, then and in that event, the responsible owner, contractor, or both, shall be liable for a fine of not less than seventy-five dollars ($75.00) nor more than seven hundred fifty dollars ($750.00) and one hundred (100) percent of the usual permit fee in addition to the required permit fee. Each day a violation continues shall be deemed a separate offense."
   Delete Section 109.6 and replace as follows:
   “109.6 Refunds. The code official shall authorize the refunding of fees as follows:
   1.   The full amount of any fee paid hereunder which was erroneously paid or collected.
   2.   Not more than 90 percent of the permit fee paid when no work has been done under a permit issued in accordance with this code.
   3.   No part of the plan review fee paid shall be refunded when the plan review has been completed and the application for permit is withdrawn. The code official shall not authorize the refunding of any fee paid, except upon written application filed by the original permittee not later than 180 days after the date of fee payment."
   Delete Section 113.1 and replace as follows:
   "113.1 General. In order to hear and decide appeals of orders, decisions or determinations made by the building official relative to the application and interpretation of this code, the village board of trustees shall be the board of appeals. Therefore, for the purposes of this code, the board of appeals shall be construed to mean the village board of trustees. The building official shall be an ex officio member of said board but shall have no vote on any matter before the board. When a quorum is present, the board shall modify, reverse, or uphold the decision of the code official by a concurring vote of the majority of members present at the meeting. The board of appeals shall adopt rules of procedure for conducting its business and shall render all decisions and findings in writing to the appellant with a duplicate copy to the building official. The building official shall take immediate action in accordance with the decision of the board."
   Delete Section 113.3 in its entirety.
   Delete Section 114.4 and replace as follows:
   "114.4 Violation Penalties, Court Costs and Legal Fees. Any person who violates a provision of this code or fails to comply with any of the requirements thereof or who erects, constructs, alters or repairs a building or structure in violation of the approved construction documents or directive of the building official, or of a permit or certificate issued under the provisions of this code, shall be subject to a fine of not less than seventy-five dollars ($75.00) nor more than seven hundred fifty dollars ($750.00). Each day a violation continues shall be deemed a separate offense. In the event noncompliance with this code necessitates litigation, any person who violates a provision of this code shall be liable for court costs and reasonable attorney's fees incurred by the village of Hampshire."
   Delete Section 115.3 and replace as follows: "115.3 Unlawful Continuance, Court Costs and Legal Fees. Any person who shall continue any work after having been served with a stop work order, except such work as that person is directed to perform to remove a violation or unsafe condition, shall be subject to a fine of not less than seventy-five dollars ($75.00) nor more than seven hundred fifty dollars ($750.00). Each day a violation continues shall be deemed a separate offense. In the event noncompliance with this code necessitates litigation, any person who violates a provision of this code shall be liable for court costs and reasonable attorney's fees incurred by the village of Hampshire."
   Add New Section “429 Vacant Buildings”
   “429.1 Maintenance of Vacant Buildings. All windows, doors, and glass areas of nonresidential buildings or structures, or portions thereof, that are vacant for a period of 14 days or more shall be treated to prevent any view into the interior of the building or structure by either of the following methods:
   1.   The uniform use of horizontal or vertical blinds, which blinds shall be either white or opaque in color; or
   2.   The use of professionally applied adhesive film.
   No other method to prevent any view into the interior of a vacant nonresidential building or structure, including without limitation the use of window soap, boards, paper, or plastic sheeting, shall be permitted unless approved by the building code official."
   2.1.1.1.1 Add new Section 901.6.3.1 Fire Alarm and Fire Sprinkler Maps and Legends:
   “Provide Fire Alarm device and location maps and fire sprinkler device and location maps, that include all devices, equipment, door numbers, riser coverage areas and information as requested by the Fire Code Official, at the fire alarm panel, every annunciator panel, and each door where there is an approved key box installed.”
   Add the following paragraph to the end of the current code requirements:
   “An automatic sprinkler system shall be provided throughout all group B occupancies and buildings.”
   903.2.1 1 Delete the following words and conditions in 903.2.1.1 Group A-1:
   “...where one of the following conditions exists:
   1.   The fire area exceeds 12,000 square feet
   2.   The fire area has an occupant load of 300 or more
   3.   The fire area is located on a floor other than a level of exit discharge serving such occupancies
   4.   The fire area contains a multiple-theater complex”
   Add the following new condition to 903.2.1.1 Group A-1:
   “903.2.1.1 Group A-1
   An automatic sprinkler system shall be provided throughout all group A-1 occupancies and buildings."
   Delete the following words and conditions in 903.2.1.2 Group A-2:
   “...where one of the following conditions exist:
   1.   The fire area exceeds 5,000 square feet
   2.   The fire area has an occupant load of 100 or more
   3.   The fire area is located on a floor other than a level of exit discharge serving the occupancy"
   Add the following new condition to 903.2.1.2 Group A-2
   “903.2.1.2 Group A-2
   An automatic sprinkler system shall be provided throughout all group A-2 occupancies and buildings.”
   Delete the following words and conditions in 903.2.1.3 Group A-3:
   “...where one of the following conditions exist:
   1.   The fire area exceeds 12,000 square feet
   2.   The fire area has an occupant load of 300 or more
   3.   The fire area is located on a floor other than a level of exit discharge serving the occupancy"
   Add the following new condition to 903.2.1.3 Group A-3:
   “903.2.1.2 Group A-3
   An automatic sprinkler system shall be provided throughout all group A-3 occupancies and buildings"
   Delete the following words and conditions in 903.2.1.4 Group A-4:
   “...where one of the following conditions exist:
   1.   The fire area exceeds 12,000 square feet
   2.   The fire area has an occupant load of 300 or more
   3.   The fire area is located on a floor other than a level of exit discharge serving the occupancy"
   Add the following new condition to 903.2.1.4
   “903.2.1.4 Group A-4
   An automatic sprinkler system shall be provided throughout all group A-4 occupancies and buildings."
   Delete Section 903.2.1.5 in its entirety and replace as follows:
   “903.2.1.5 Group A-5. An automatic sprinkler system shall be provided throughout all group A-5 occupancies.”
   Delete in 903.2.1.6 in its entirety and replace with as follows:
   “903.2.1.6 Assembly Occupancies on roofs. Where an occupied roof has an assembly occupancy, all floors between the occupied roof and the level of exit discharge shall be equipped with an automatic sprinkler system in accordance with all applicable sections of this code.”
   903.2.1.7 Delete the follow word/number from the section 903.2.1.7:
   “903.2.1.7 Multiple fire areas. Delete 300 or more.”
   903.2.2   Delete in 903.2.2 in its entirety and replace with as follows:
   “Section 913.2.2 Ambulatory care facilities. An automatic sprinkler system shall be provided throughout all buildings that contain ambulatory care facilities. In buildings where ambulatory care is provided on levels other than the level of exit discharge, an automatic sprinkler system shall be installed throughout the entire floor as well as all floors below where such care is provided, and all floors between the level of ambulatory care and the nearest level of exit discharge, the level of exit discharge, and all floors between the level of exit discharge.”
   903.2.3 Delete in 903.2.3 in its entirety and replace with as follows:
   “903.2.3 Group E. An automatic sprinkler system shall be provided throughout all group E occupancies.”
   903.2.4 Delete in 903.2.4 in its entirety and replace with as follows:
   “903.2.4 Group F-1. An automatic sprinkler system shall be provided throughout all buildings containing a group F-1 occupancy.”
   903.2.4 1 Delete in 903.2.4.1 in its entirety and replace with as follows:
   “903.2.4.1 Woodworking operations. An automatic sprinkler system shall be provided throughout all buildings containing a group F-1 occupancy that conduct woodworking operations.”
   903.2.5.3 Delete in 903.2.5.3 in its entirety and replace with as follows:
   “903.2.4.1 Pyroxylin Plastics. An automatic sprinkler system shall be provided in buildings, or portions thereof, where cellulose nitrate film or pyroxylin plastics are manufactured, stored, or handled.”
   903.2.6 Delete in the exceptions 1,2 and 3, in their entirety.
   903.2.7 Delete in the exceptions 1, 2, 3 and 4, in their entirety.
   903.2.9.2 Delete Section 903.2.9.2 in its entirety and replace as follows:
   “903.2.9.2 Bulk Storage of tires. Buildings and structures where there is a storage of tires shall be equipped throughout with an automatic sprinkler system.”
   903.2.11 1 Delete Section 903.2.11.1 in its entirety and replace as follows:
   “903.2.11.1 Stories without openings. An automatic sprinkler system shall be provided throughout all stories and buildings, including basements and stories below grade and for all stories.”
   903.2.11.3 Amend the section 903.2.11.3 as follows:
   “An automatic fire sprinkler system shall be provided in all buildings regardless of height and occupant load as required in other sections of this code.”
   903.2.13 Add the following new Section:
   “An automatic fire sprinkler system shall be provided throughout all stories and buildings, including basements of all B-Business Use Occupancies.”
   903.2.14 Add the following new Section:
   “An automatic fire sprinkler system shall be installed throughout all stories and buildings, including basements, of all F-2 Factory Use Occupancies.”
   903.2.15 Add the following new Section:
   “All new buildings other than those that are noted in Village Ordinance for not requiring fire sprinklers, shall be required to have an approved fire sprinkler system.”
   903.4.1   Amend Section 903.4.1 to the following, and the current exceptions have no change:
   “Alarm, supervisory and trouble signals shall be distinctly different and shall be automatically transmitted to an approved supervising station, central station or remote station. Alarms shall then be reported to the Communications Center of the Fire Protection District.”
   Add the following additional requirements to the current code section 903.4.2 Alarms:
   “1.   A 75cd minimum blue, weather-proof strobe light above the fire department sprinkler connection and adjacent to the outside sprinkler alarm bell, that activates on sprinkler waterflow.
   2.   A 75cd minimum, red strobe light outside the main building entrance that activates on all general fire alarm activations”
   904.3.5   Amend Section 904.3.5 Monitoring to the following:
   “An automatic fire-extinguishing system shall be monitored by a building fire alarm system in accordance with NFPA 72.”
   905 3.1 Amend Section 905.3.1 Height as follows:
   “Class III standpipe systems shall be installed throughout buildings or structures where any of the following conditions exist:
   1.   Three or more stories are above grade plane
   2.   The floor level of the highest story is located thirty (30) feet or more above the lowest level of the fire department access.
   3.   Any floor level that is located below the highest level of fire department vehicle access or below grade."
   All current exceptions in the code (1 through 7) remain the same.
   907.1 Add the following paragraph to the current Section 907.1 General
   “Provide Fire Alarm device and location maps and fire sprinkler device and location maps, that include all devices, equipment, door numbers, riser coverage areas and information as requested by the Fire Code Official, at the fire alarm panel, every annunciator panel, and each door where there is an approved key box installed.”
   907.2 Add the following to the current Section 907.2
   “An approved manual fire alarm system, approved automatic fire alarm with fire detection (smoke) system shall be installed in any and all new buildings and structures that requires a building permit. If there is an automatic fire sprinkler system, then an automatic fire alarm system is only required if it is required in the adopted code or amendments and also to monitor a fire suppression/sprinkler system and other fire protection installations.
   An approved manual fire alarm system, approved automatic fire alarm with fire detection (smoke) system shall be installed, in any and all buildings and structures undergoing remodeling, renovations, installations and like changes (painting, carpeting, flooring and cosmetic changes not included) that requires a building permit. If there is an automatic fire sprinkler system, then a fire alarm system is only required if it is required in the adopted code or amendments and also to monitor a fire suppression/sprinkler system and other fire protections installations.
   If there is a change in occupancy classification of a building, with or without renovations, an approved manual fire alarm system, automatic fire alarm with fire detection (smoke) system, and an approved fire sprinkler system shall be installed. When installation of a fire sprinkler system is required by this section, installation shall be required on all floors of the occupied space as required by the building regulations. A fire alarm system will be required to monitor a fire suppression/sprinkler system and other fire protection installations.
   If the renovation of any building or structure undergoing remodeling, renovations, installations and like changes (painting, carpeting, flooring and cosmetic changes not included) that requires a building permit exceeds 50% of the occupied single-floor area, then an approved fire sprinkler system shall be installed. When installation of a fire sprinkler system is required by this section, installation shall be required on all floors of the occupied spaces as required by the building regulations. A fire alarm system will be required to monitor a fire suppression/sprinkler system and other fire protection installations.
   Exception: Upon renovation exceeding 50% of the occupied single-floor area of a building containing a Group B or M occupancy, installation of a fire sprinkler system shall only be required if the occupied single-floor area exceeds 5,000 square feet.
   The automatic fire detectors shall be smoke detectors. Where ambient conditions prohibit installation of automatic smoke detection, other automatic fire detections shall be allowed. A change in zoning and/or occupancy use type (according to the IBC) will also require an approved automatic fire alarm and approved automatic fire detection system (smoke detection and manual pull stations).”
   (The remainder of the Section remains the same)
   Add the following to the end of 907.2: "If the fire alarm control panel is not located at the main entrance to the building or space, then an annunciator panel shall be provided at the front entrance and depending upon size of the building, at additional locations as determined by the Fire Code Official."
   907.6.4 Add the following to Section 907.6.4 Zones
   Delete the wording "Each Floor shall be zoned separately, and a zone shall not exceed 22,500 square feet. The length of any zoned shall not exceed 300 feet in any direction" and replace with "All fire alarm systems, required or voluntary installation, shall be UL listed addressable fire alarm panels and installed in accordance with NFPA 72 and NFPA 70 and shall utilize approved radio signal for transmitting all types of alarm conditions from the fire alarm panel to the supervising station."
   907.6.5.1 Add the following new section 907.6.5.1 HVAC Remote Test and Reset Switches:
   "All HVAC equipment required to have smoke detection shutdown shall have a remote test and reset switch located under that piece of equipment, if an RTU, or under that RTU and no higher than 6 feet off the finished floor. The remote test and reset switch for a non-RTU can be placed at the equipment and in both cases the remote test and reset switch can be located at the Fire Alarm Control Panel. The switch shall be labeled as such and the corresponding piece of HVAC equipment shall be labeled the same as the remote test and reset switch. Activation of any Duct smoke detector shall transmit a general (true) fire alarm."
   912.1 Add the following Sentence to the end of the current code section:
   "The Fire Department Connection shall also be of a type as required by the Fire Code Official."
   1101.1 Add the following at the end of Section 1101.1:
   “When there is a conflict between (i) this Chapter 11 of the International Building Code and (ii) the Illinois Environmental Barriers Act, 410 ILCS 25/1 et seq., and the administrative rules adopted thereunder contained in 71 III. Adm. Code 400, 110 et seq., also known as or the "Illinois Accessibility Code", the stricter of the two requirements shall be used.”
   1301.1 Amend Section 1301.1 as follows:
   “Section 1301.1 Criteria. Buildings shall be designed and constructed in accordance with the 2018 International Energy Conservation Code or the most current State of Illinois Energy Conservation Code.”
   1808.1.1 Add the following new Section 1808.1.1:
   "1808.1.1 Wood and straw footings and foundations. The use of wood or straw footings or foundations shall not be allowed. All references to wood or straw footings or foundations in this Chapter and International Building Code shall be deleted."
   1808.1.2 Add the following new Section 1808.1.2:
   "1808.1.2 Frost depth. The minimum frost depth to be used for footing design is 42 inches."
   2701.2 Add the following new Section 2701.2:
   “2701.2 NFPA 70 Electrical Code. Amendments to NFPA 70. The 2017 edition of NFPA 70 (National Electrical Code) have been adopted for use by the Village pursuant to Article 7 of this Title.”
   2901.1 Delete Section and replace with the following:
   “2901.1 Scope. The provisions of the Illinois Plumbing License Law, 225 ILCS 320/0.01 et seq. and the regulations adopted thereunder in 68 III. Admin. Code 750.one hundred (100) et seq. and 77 III. Admin. Code 890.110 et. Seq. (collectively "Illinois Plumbing Law") shall regulate the licensing of plumbers, the registration of irrigation contractors, and the design and installation of plumbing systems, including but not limited to sanitary and storm drainage, sanitary facilities, water supplies and storm water and sewage disposal. The Village has adopted the Illinois Plumbing Law with amendments pursuant to Article 6 of this Title.”
   2901.2 Add a new Section 2901.2 as follows:
   “2901.3 Amendments to Illinois Plumbing Law. The Illinois Plumbing Law is amended as set forth in Article 6 of this Chapter."
   3001.1 Amend Section 3001.1 to read as follows:
   “3001.1 Scope. All Elevator and Conveyance design, installation, construction, operation, inspection, testing, maintenance, alteration and repair of elevators and conveyances shall comply with Section 35 of the Elevator Safety and Regulation Act (225 ILCS 312/35) of the State of Illinois and all adopted administrative rules including but not limited to Illinois Administrative Code 1000 and all stated references in that Act and Administrative Code shall be adopted as reference as indicated in those documents. This Chapter thirty (30) shall be applied if it is more restrictive than the Illinois Elevator Safety and Regulation Act.”
   3110.4 Add new Section 3110.1.4:
   “3110.4 Vehicular gates. All automatically controlled gates across any access points to or around any property, regardless of occupancy type, shall be equipped with an operational override key switch or strobe sensor for emergency access. The strobe sensor or key switch type must be approved by the Fire Code Official. If a key lock is going to be utilized then a key box, as utilized by the Fire Department, shall be installed at the gate and a key to the lock or for an override switch shall be in the box. A knox lock can be used in lieu of the knox box.”
   3201.5 Add the following new Section 3201.5:
   “3201.5 Additional site plan requirements. Additional site plan requirements are to be determined by the building official, or his or her authorized designee for each permit, and may include one or more of the following:
   1.   Fencing is to be installed as listed on the approved site plan and shall include a gate for access and ability to enclose the site at the end of each working day. Commercial fencing is to be a minimum of six-foot high chain link fence properly supported.
   2.   All open excavated holes and drops are to be completely encircled as a minimum with a four-foot-high safety fencing;
   3.   Silt fencing is required to prevent silt from causing a nuisance to neighboring properties, discharge into the storm sewer system or creating a hazard.
   4.   A construction drive shall be installed at the start of the job with a gravel base to provide contractor Parking to the extent possible to prevent mud and debris from being tracked onto streets.
   5.   Dirt and debris are to be kept off of street at all times a dumpster or trash container shall be provided throughout construction.
   6.   A portable toilet shall be maintained at all times, except where the building owner allows use of the existing facility. The portable toilet is to be placed to least impact the neighbors and a minimum of 10 feet off the lot line;
   7.   All sidewalks damaged during construction are to be replaced. In areas where a new home is constructed all the sidewalks along the property are to be replaced unless determined otherwise by the building official, or his or her authorized designee. Damaged sidewalks are to be replaced with a minimum of a four inch bed of compacted gravel and a minimum of five inch thick concrete panel. Sidewalk panels in drive areas are to be replaced with a minimum of seven-inch thick concrete.
   8.   Sidewalks damaged during construction shall be topped with temporary bituminous pavement until final concrete can be placed.
   9.   Granular back fill shall be required for all street, road edge, sidewalk, driveway, slab, or patio areas as determined by the building official, or his or her authorized designee.
   10.   Any street excavation shall be topped with a temporary bituminous pavement within 48 hours of excavation. A permanent minimum of three (3) inch bituminous layer, compacted in two lifts, with saw cut edges, is required as part of the final approval, (a road opening fee per the current fee schedule will be accessed if road opening is performed).
   11.   Damage to Parkway or neighbor's property due to construction shall be repaired as soon as weather permits.
   12.   Traffic and Parking requirements as noted on plan are to be followed throughout the construction process.
   13.   Temporary electric services are to be installed to prevent the use of generators.
   14.   Tree protection is to be installed per the site plan and may include (fencing, wrapping of trunk, root cutting before excavation trimming limbs for access, feeding, aerating, and directional boring under trees with services) as well as requirements of the tree preservation section.
   15.   Materials are to be stored on private property, storage of materials in the public right of way is not permitted unless prior approval is granted by the Village.
   16.   Dust of any type is to be controlled by use of water or other forms of containment so not to cause a nuisance and use of wet saws as required by village ordinance.
   17.   Sump discharge is to have one or more of the following: open site connection, storm sewer connection, drywell or discharge to approved area on the property. (Sump water will not be allowed to discharge to a location that will cause a hazard in freezing conditions such as drives, sidewalks, or streets).
   18.   As -built drawings are required for all exterior water, sanitary, and storm service lines from the foundation wall of the structure being serviced to the point of connection with the existing service stub or existing main. The as built drawing is required regardless of the length of the installation of the new portion of the utility service.
   18.1 The drawing must be to scale and be no smaller than 1" = 20'. The scale must be indicated on the submitted drawings.
   18.2 The drawing must be neat, clean and legible. Multiple service lines can be shown on the same drawing.
   18.3 The minimum acceptable drawing size is 8-1/2" x 11".
   18.4 The pipe size and type must be indicated for each service line.
   18.5 The Location of the installed service line(s) must be tied to a minimum of two exterior property corners and two exterior foundation corners within an accuracy of one (1) foot.
   18.6 The locations of all fittings, cleanouts, and B-box's must be identified within an accuracy of one (1) foot.
   18.7 The depth of the utility service below final grade must be indicated at all grades and at a minimum of every fifty (50) feet along the length of each installed service.
   18.8 All prominent topographical features such as exterior build foundations lines, sidewalks, back of curb, edger of pavement and existing manholes must be indicated if these features are within 20 feet of any portion of the utility service line work covered by the building permit.
   18.9 The means of connecting the new portion of the utility line to the existing main or stub must be identified (Coupling types, tees, wyes etc.)
   18.10 The lower right-hand corner of the submitted drawing must contain the following information: Street address where the work is being performed; the building permit number; the date of the sketch preparation; the name and address and telephone number of the general contractor and subcontractor.
   19.   Every new building and buildings with substantial renovation or as required by the building official, or his or her authorized designee, shall install a conduit from the water meter location to the street side exterior of the building. This conduit shall be used for the remote MXU wiring to the water meter.
   20.   All new exterior sanitary sewer cleanout covers shall be of a type and material that can be repeatedly driven over and shall not be made of a PVC material or other material that cannot withstand the weight of vehicles.
   21.   Utility Connections. All service utility connections shall be discontinued and capped at the main in accordance with the rules and requirements of the authority having jurisdiction."
   Appendix C: Adopted by reference.
   Appendix D: Adopted by reference.
   Appendix F: Adopted by reference.
   Appendix N: Adopted by reference. (Ord. 22-27, 10-6-2022; amd. Ord. 23-03, 3-2-2023; Ord. 23-38, 12-21-2023)