§ 153.44 WALL FINISHES.
   (A)   Interior and exterior surfaces of bale walls shall be protected from mechanical damage, flame, animals, and prolonged exposure to water. Bale walls adjacent to bath and shower enclosures shall be protected by a moisture barrier.
   (B)   Cement stucco shall be reinforced with galvanized woven wire stucco netting or an acceptable equivalent. Such reinforcement shall be secured by attachment through the wall at a maximum spacing of 24 inches horizontally and 16 inches vertically, using a method approved by the building official.
   (C)   Where bales abut other materials, the plaster/stucco shall be reinforced with galvanized expanded metal lath, or an acceptable equivalent, extending a minimum of six inches onto the bales.
   (D)   Earthen and lime-based plasters may be applied directly onto the exterior and interior surface of bale walls without reinforcement, except where applied over materials other than straw. Weather-exposed earthen plasters shall be stabilized using a method approved by the building official.
   (E)   Lime based plasters may be applied directly onto the exterior surface of bale walls without reinforcement, except where applied over materials other than straw.
(Res. 96-17, passed 12-12-1996)