§ 10-9-5 ELECTRICAL REQUIREMENTS, GFI.
   (A)   All electrical equipment including power supply cords used with all pools shall be protected by ground fault circuit interrupters.
   (B)   (1)   A ground fault circuit interrupter (GFI) protected receptacle shall be installed no closer than five feet nor farther than 20 feet from outside wall of pool.
      (2)   No other receptacles shall be located within ten feet of pool unless separated by a barrier.
(Ord. 13-11, passed 10-1-2013) Penalty, see § 10-9-99