Backflow prevention is required when one or more of the following situations apply:
(A) By Order of the Indiana Department of Environmental Management in accordance with 327 IAC 8-10-4(d).
(B) By order of the Utility, provided that notice is given that specifies the nature of the customer activity that necessitates designation of the facility as a cross-connection hazard and a date by which the facility must comply with the order.
(C) For new construction of any of the following types of facilities:
(1) Facilities that present a cross-connection hazard as designated in § 52.32(A)(7);
(2) Proposed facilities with unknown tenants, commonly known as "spec buildings";
(3) Facilities that plan to use carbonated fountain soft drink machines;
(4) Facilities with a secondary source of supply, including but not limited to, emergency use, fire prevention, irrigation, or economics; or
(5) Facilities that plan to use fire protection service lines in the facility.
(D) For existing facilities proposing the following types of modifications:
(1) Installation of a new customer service line if the facility is one of the types of facilities identified in § 52.31(C);
(2) Modifications to a facility's customer service line if the facility is one of the types of facilities identified in § 52.31(C); or
(3) Modifications involving the installation of additional or larger capacity meters if the facility is one of the types of facilities identified in § 52.31(C).
(E) For any existing facility with a cross connection.
(F) For any use of temporary water service.
(Ord. G-6-18, passed 3-27-18)