§ 93.113  PORTABLE FIRE EXTINGUISHERS AND WHERE REQUIRED.
   (A)   Except for private dwellings, portable fire extinguishers shall be installed and maintained in all occupancies built and placed in service after January 1, 2004, as set forth in NFPA Standard No. 10, currently adopted by the Commission.
   (B)   Notwithstanding other provisions of this chapter, portable fire extinguisher equipment required for Class 1 residential apartment buildings shall be as follows:
      (1)   A minimum 2-A, 10BC Rated Dry Chemical Extinguisher shall be placed at intervals of 75 feet travel distance on each floor level in all common areas of all apartments. The requirements of this division (B)(1) are satisfied if each individual apartment shall have a minimum 2-A, 10BC Rated Dry Chemical Extinguisher installed in the unit; and
      (2)    Each laundry room and storage area shall have a minimum 2-A, 10BC Rated Dry Chemical Extinguisher. Each clubhouse and maintenance building or room shall have a minimum 2-A, 10BC Rated Dry Chemical Extinguisher placed at intervals of 75 feet travel distance.  Notwithstanding the provisions of this division (B)(2), laundry rooms and storage areas contiguous to the common corridors which have proper extinguishers placed at intervals of 75 feet travel distance are exempt from this division (B)(2).
      (3)   Any facility that performs a cooking process that produces grease laden vapors, shall have, in addition to an exhaust hood suppression system, at least one “K” class (potassium acetate, wet chemical) portable fire extinguisher.
(Ord. CO-03-05, passed 8-25-03; Am. Ord. 14-08, passed 8-11-14)  Penalty, see § 93.999