§ 50.21 REFRIGERATING UNIT CONDENSERS AND COOLING JACKETS.
   Except where potable water provided for a refrigerator condenser or cooling jacket is entirely outside the piping or tank containing a toxic refrigerant, the inlet connection shall be provided with an approved check valve. Also adjacent to and at the outlet side to the check valve, an approved pressure relief valve set to relieve at five psi above the maximum water pressure at the point of installation shall be provided if the refrigeration units contain more than 20 pounds of refrigerants.