1336.602 HEATING FACILITIES.
   1336.602.1 Facilities Required.
   Heating facilities shall be provided in structures as required by this section.
   1336.602.2 Residential Occupancies.
   Dwellings shall be provided with heating facilities capable of maintaining a room temperature of 65°F (18°C) in all habitable rooms, bathrooms and toilet rooms. Cooking appliances shall not be used to provide space heating to meet the requirements of this section.
   1336.602.3 Heat Supply.
   Every owner and operator of any building who rents, leases or lets one or more dwelling unit, rooming unit, dormitory or guestroom on terms, either expressed or implied, to furnish heat to the occupants thereof shall supply heat to maintain a minimum temperature of 65°F (18°C) in all habitable rooms, bathrooms and toilet rooms.
   1336.602.4 Occupiable Work Spaces.
   Indoor occupiable work spaces shall be supplied with heat to maintain a minimum temperature of 65°F (18°C) during the period the spaces are occupied.
   1336.602.5 Room Temperature Measurement.
   The required room temperatures shall be measured 3 feet (915 mm) above the floor near the center of the room and 2 feet (610 mm) inward from the center of each exterior wall.
(Ord. 21-15. Passed 6-15-15.)