§ 92.047 INSTALLATION AND PLACEMENT REQUIREMENTS.
   (A)   Not less than one approved carbon monoxide detector shall be installed in each residential unit. The detector shall be installed within 40 feet of all rooms used for sleeping purposes.
   (B)   In every hotel and motel, one approved carbon monoxide detector shall be installed for every 10,000 square feet of floor area, or fraction thereof:
      (1)   On every floor on which a fossil fuel-burning appliance, boiler, or furnace is located; and
      (2)   On every floor on which sleeping rooms are heated by any type of warm air heating plant that burns fossil fuel. Floor area shall be computed separately for each floor. Each dwelling unit employing space heating equipment that is located within the dwelling unit and that burns fossil fuel shall be equipped with at least one carbon monoxide detector.
(Prior Code, § 92.067) (Ord. 0-94-0026, passed - -1994) Penalty, see § 92.999