§ 93.28 DRY HYDRANTS.
   (A)   Dry hydrants may have to be installed when an available static water supply is available in the development. This should be an additional water supply for fire protection. Dry hydrants will not be substituted when standard fire hydrants are required by the FPBSC adopted code and this section.
   (B)   Dry hydrants will be placed within eight feet of the roadway and 30 to 36 inches above finished grade.
   (C)   All dry hydrants will be painted red in color.
   (D)   The connection is to be a six inch female connection National Standard Thread with cap. All installations will be under NFPA and the FPBSC adopted codes.
   (E)   All dry hydrants will be identified with a sign stating Fire Department Dry Hydrant - Do Not Block' which will be affixed to the connection.