(A) Several parameters or conditions may require the village to begin the WSRP. These include but may not be limited to significant reductions in well water levels, a significant increase in pump run times for the predetermined total flow at the well(s), contaminants in the water system, act of terrorism, vandalism, main breaks and natural disasters.
(B) If the factors listed above reduce well water levels or pump run times or by any event or combination of events prevent the water system from delivering water, WSRP phases will be enacted in the following order:
(1) Phase I will be enacted if a 20% reduction in normal well water levels is noted or if pump run times increase 20% in order to maintain previous rates or any other event which causes a 20% reduction is the water system's capacity.
(2) Phase II will be enacted if a 40% reduction in normal well water levels is noted or if pump run times increase 40% in order to maintain previous rates or any other event which causes a 40% reduction in the system's capacity.
(3) Phase III will be enacted if a 60% reduction in normal well water levels is noted or if pump run times increase 60% in order to maintain previous rates or any other event which causes a 60% reduction in the system's capacity.
(Ord. passed 9-18-2008; Am. Ord. passed 7-17-2010; Am. Ord. passed 2-23-2018)