§ 33.336 HORIZONTAL AND VERTICAL CLEARANCE REQUIREMENTS.
   (A)   (1)   A minimum outside-to-outside horizontal clearance of five feet shall be maintained between the sewer mains and structures and adjacent non-potable water and storm water underground utility mains and structures.
      (2)   Provide eight feet outside-to-outside separation from planter strips and six feet separation from continuous sidewalk and concrete curbs unless approved by the Engineer.
   (B)   A minimum horizontal clearance of ten feet shall be maintained between the sewer main and parallel water mains unless approved in advance by the Engineer.
   (C)   (1)   A minimum vertical clearance between the sewer main and adjacent, non-potable water underground utility mains shall be six inches.
      (2)   Pipe couplings are not allowed within the trench.
      (3)   Greater clearance may be required by the District.