9-2-2-4: FIRE CODE AMENDMENTS:
The following additions, insertions and changes shall further apply and shall supersede any and all references listed within the international fire code, 2012 edition:
Section 101.1 Insert "Village of Campton Hills".
Section 105.8 Unique Construction: When a project has unique features, unusual construction sequences or out of the ordinary construction techniques, the building department shall have the authority to require additional documentation to determine code compliance. The building department may also add additional fees to the building permit based on additional inspections required or to cover the cost of specialized inspections or outside inspection or testing agencies.
(2013 Code § 11-1-8)
Unique features or unusual construction sequence is a project where the use of features or sequences, which create the need for additional inspections other than those normally, requested by the building and zoning officer. The features, or a sequence of operations, which creates additional inspections, can create this.
Section 108 Board Of Appeal: Delete 108.1 through 108.3 and insert:
"See building code amendments to section 113.".
(2013 Code § 11-1-8; amd. 2016 Code)
Section 109.3 Violation Penalties: Insert the following:
Penalties shall be determined by ordinance by the village board.
Section 111.4 Stop Work Orders: Insert the following:
Penalties shall be determined by ordinance by the village board.
(2013 Code § 11-1-8)
Section 307: See subsection 5-1-2C of the village code for additional open burning requirements.
(2013 Code § 11-1-8; amd. 2016 Code)
Section 901.11 Add the following:
All water flow switches, valve supervision, trouble signals, fire alarm systems shall transmit an alarm to a location approved by the code official.
Sections 903.2.1 through 903.2.10.1 Delete sections 903.2.1 through 903.2.10.1 and add the following:
See section 9-1-6 of the village code for the sprinkler requirements.
Section 903.4.2 Add the following sentence:
Provide a strobe above the fire department connection for all sprinkler and standpipe systems.
Section 903.6 Add new section 903.6 Sprinkler System Design Criteria:
Sprinkler hydraulic designs for NFPA 13 and NFPA 13R systems shall be designed with a minimum of a five (5) pound difference between the sprinkler system design including hose requirements and the available water supply. The five (5) pound safety factor shall be applied to the water flow test after any adjustments for a seasonal low.
Section 5704.2.9.6.1 As allowed in the zoning ordinance as may be amended.
Section 5706.2.4.4 As allowed in the zoning ordinance as may be amended.
Section 5806.2 As allowed in the zoning ordinance as may be amended.
Section 6104.2 As allowed in the zoning ordinance as may be amended.
Referenced standards:
Delete the references to the international plumbing code.
Adopt the following appendices: B, C, D, E, F, G, H.
(2013 Code § 11-1-8)