(A) General requirements. It shall be the responsibility of building and premises owners to maintain all backflow preventers and vacuum breakers within the building or on the premises in good working order and to make no piping or other arrangements for the purpose of bypassing backflow devices.
(B) Backflow preventers.
(1) (a) Periodic testing and inspection schedules shall be established by the Manager for all backflow preventers and the interval between such testing and inspections and overhauls of each device shall be established in accordance with the age and condition of the device.
(b) Inspection intervals shall not exceed one year, and overhaul intervals shall not exceed five years.
(2) (a) These devices shall be inspected frequently after the initial installation to assure that they have been installed properly and that debris resulting from the installation has not interfered with the functioning of the device.
(b) The testing procedures shall be in accordance with the manufacturer’s instructions when approved by the Manager.