Where public water supply is within reasonable distance, as determined by the Planning Board, the subdivider or developer shall construct a system of water mains together with all appurtenances, such as valves and curb connections at each lot within said subdivision, and connect with such public water supply. All water mains shall be cast iron pipe and conform to ASA Specifications, A 21.6 (AWWA C 106). No water line less than 6-in. in diameter will be permitted in residential areas and 8-in. in a commercial or business district. Larger mains shall be required for manufacturing districts, depending on type of industry. Fire hydrants of the type approved by the Village of Bradford shall be placed not over 500 feet apart. Reference the Village of Bradford Standard Specifications and Drawings for further requirements.
(Ord. 0-5-73. Passed 6-5-73.)