Loading...
Sec. 10-58. Plumbing facilities and fixture requirements.
   (a)   General.
      (1)   Scope. The provisions of this section shall govern the minimum plumbing systems, facilities, and plumbing fixtures to be provided.
      (2)   Responsibility. The owner of the structure shall provide and maintain such plumbing facilities and plumbing fixtures in compliance with these requirements. A person shall not occupy as owner-occupant or permit another person to occupy any structure or premises which does not comply with the requirements of this section.
   (b)   Required facilities.
      (1)   Dwelling units. Every dwelling unit shall contain its own bathtub or shower, lavatory, water closet, and kitchen sink which shall be maintained in a sanitary, safe working condition. The lavatory shall be placed in the same room as the water closet or located in close proximity to the door leading directly into the room in which such water closet is located. A kitchen sink shall not be used as a substitute for the required lavatory.
      (2)   Rooming houses. At least one water closet, lavatory and bathtub or shower shall be supplied for each four rooming units.
      (3)   Hotels. Where private water closets, lavatories and baths are not provided, one water closet, one lavatory and one bathtub or shower having access from a public hallway shall be provided for each ten occupants.
      (4)   Employees' facilities. A minimum of one water closet, one lavatory, and one drinking facility shall be available to employees.
         a.   Drinking facilities. Drinking facilities shall be a drinking fountain, water cooler, bottled water cooler or disposable cups next to a sink or water dispenser. Drinking facilities shall not be located in toilet rooms or bathrooms.
   (c)   Toilet rooms.
      (1)   Privacy. Toilet rooms and bathrooms shall provide privacy and shall not constitute the only passageway to a hall or other space, or to the exterior. A door and interior locking device shall be provided for all common or shared bathrooms and toilet rooms in a multiple dwelling.
      (2)   Location. Toilet rooms and bathrooms serving hotel units, rooming units or dormitory units or housekeeping units, shall have access by traversing not more than one flight of stairs and shall have access from a common hall or passageway.
      (3)   Location of employee toilet facilities. Toilet facilities shall have access from within the employees' working area. The required toilet facilities shall be located not more than one story above or below the employees' working area and the path of travel to such facilities shall not exceed a distance of 500 feet (152 m). Employee facilities shall either be separate facilities or combined employee and public facilities.
      Exception: Facilities that are required for employees in storage structures or kiosks, which are located in adjacent structures under the same ownership, lease or control, shall not exceed a travel distance of 500 feet (152 m) from the employees' regular working area to the facilities.
      (4)   Floor surface. In other than dwelling units, every toilet room floor shall be maintained to be a smooth hard, nonabsorbent surface to permit such floor to be easily kept in a clean and sanitary condition.
   (d)   Plumbing systems and fixtures. 
      (1)   General. All plumbing fixtures shall be properly installed and maintained in working order, and shall be kept free from obstructions, leaks and defects and be capable of performing the function for which such plumbing fixtures are designed. All plumbing fixtures shall be maintained in a safe, sanitary, and functional condition.
      (2)   Fixture clearances. Plumbing fixtures shall have adequate clearances for usage and cleaning.
      (3)   Plumbing system hazards. Where it is found that a plumbing system in a structure constitutes a hazard to the occupants or the structure by reason of inadequate service, inadequate venting, cross connection, back-siphonage, improper installation, deterioration, or damage or for similar reasons, the Building Official shall require the defects to be corrected to eliminate the hazard.
   (e)   Water system.
      (1)   General. Every sink, lavatory, bathtub or shower, drinking fountain, water closet, or other plumbing fixture shall be properly connected to either a public water system or to an approved private water system. All kitchen sinks, lavatories, laundry facilities, bathtubs and showers shall be supplied with hot or tempered and cold running water in accordance with the Florida Building Code, Plumbing.
      (2)   Contamination. The water supply shall be maintained free from contamination and all water inlets for plumbing fixtures shall be located above the flood-level rim of the fixture. Shampoo basin faucets, janitor sink faucets and other hose bibs or faucets to which hoses are attached and left in place, shall be protected by an approved atmospheric-type vacuum breaker or an approved permanently attached hose connection vacuum breaker.
      (3)   Supply. The water supply system shall be installed and maintained to provide a supply of water to plumbing fixtures, devices, and appurtenances in sufficient volume and at pressures adequate to enable the fixtures to function properly, safely, and free from defects and leaks.
      (4)   Water heating facilities. Water heating facilities shall be properly installed, maintained and capable of providing an adequate amount of water to be drawn at every required sink, lavatory, bathtub, shower, and laundry facility at a temperature of not less than 110°F (43°C). A gas-burning water heater shall not be located in any bathroom, toilet room, bedroom or other occupied room normally kept closed, unless adequate combustion air is provided. An approved combination temperature and pressure-relief valve and relief valve discharge pipe shall be properly installed and maintained on water heaters.
   (f)   Sanitary drainage system. 
      (1)   General. All plumbing fixtures shall be properly connected to either a public sewer system or to an approved private sewage disposal system.
      (2)   Maintenance. Every plumbing stack, vent, waste and sewer line shall function properly and be kept free from obstructions, leaks and defects.
   (g)   Storm drainage.
      (1)   General. Drainage of roofs and paved areas, yards and courts and other open areas on the premises shall not be discharged in a manner that creates a public nuisance.
(Ord. No. 08-031, § 3, 11-18-08)
Sec. 10-59. Mechanical and electrical requirements.
   (a)   General.
      (1)   Scope. The provisions of this section shall govern the minimum mechanical and electrical facilities and equipment to be provided.
      (2)   Responsibility. The owner of the structure shall provide and maintain mechanical and electrical facilities and equipment in compliance with these requirements. A person shall not occupy as owner-occupant or permit another person to occupy any premises which does not comply with the requirements of this section.
   (b)   Reserved.
   (c)   Mechanical equipment.
      (1)   Mechanical appliances. All mechanical appliances, fireplaces, solid fuel-burning appliances, cooking appliances and water heating appliances shall be properly installed and maintained in a safe working condition, and shall be capable of performing the intended function.
      (2)   Removal of combustion products. All fuel-burning equipment and appliances shall be connected to an approved chimney or vent.
      Exception: This provision shall not apply to fuel-burning equipment and appliances which are labeled for unvented operation.
      (3)   Clearances. All required clearances to combustible materials shall be maintained.
      (4)   Safety controls. All safety controls for fuel-burning equipment shall be maintained in effective operation.
      (5)   Combustion air. A supply of air for complete combustion of the fuel and for ventilation of the space containing the fuel-burning equipment shall be provided for the fuel-burning equipment.
      (6)   Energy conservation devices. Devices intended to reduce fuel consumption by attachment to a fuel-burning appliance, to the fuel supply line thereto, or to the vent outlet or vent piping therefrom, shall not be installed unless labeled for such purpose and the installation is specifically approved.
   (d)   Electrical facilities.
      (1)   Facilities required. Every occupied building shall be provided with an electrical system in compliance with the requirements of this section.
      (2)   Service. The size and usage of appliances and equipment shall serve as a basis for determining the need for additional facilities in accordance with the NFPA 70 National Electrical Code. Dwelling units shall be served by a three-wire, 120/240 volt, single-phase electrical service having a rating of not less than 60 amperes.
      (3)   Electrical system hazards. Where it is found that the electrical system in a structure constitutes a hazard to the occupants or the structure by reason of inadequate service, improper fusing, insufficient receptacle and lighting outlets, improper wiring or installation, deterioration or damage, or for similar reasons, the Building Official shall require the defects to be corrected to eliminate the hazard.
   (e)   Electrical equipment.
      (1)   Installation. All electrical equipment, wiring, and appliances shall be properly installed and maintained in a safe and approved manner.
      (2)   Receptacles. Every habitable space in a dwelling shall contain at least two separate and remote receptacle outlets. Every laundry area shall contain at least one grounded-type receptacle or a receptacle with a ground fault circuit interrupter. Every bathroom shall contain at least one receptacle. Any new bathroom receptacle outlet shall have ground fault circuit interrupter protection.
      (3)   Luminaries. Every public hall, interior stairway, toilet room, kitchen, bathroom, laundry room, boiler room, and furnace room shall contain at least one electric luminaire.
   (f)   Elevators, escalators and dumbwaiters.
      (1)   General. Elevators, dumbwaiters, and escalators shall be maintained in compliance with Florida statutes and ASME A17.1. The most current certification of inspection shall be on display at all times within the elevator or attached to the escalator or dumbwaiter, or the certificate shall be available for public inspection in the office of the building operator. The inspection and tests shall be performed at not less than the periodical intervals listed in ASME A17.1, Appendix N, except where otherwise specified by the authority having jurisdiction.
      (2)   Elevators. In buildings equipped with passenger elevators, at least one elevator shall be maintained in operation at all times when the building is occupied.
      Exception: Buildings equipped with only one elevator shall be permitted to have the elevator temporarily out of service for testing or servicing.
   (g)   Duct systems.
      (1)   General. Duct systems shall be maintained free of obstructions and shall be capable of performing the required function.
(Ord. No. 08-031, § 3, 11-18-08)
Sec. 10-60   Fire safety requirements.
   (a)   General.
      (1)   Scope. The provisions of this section shall govern the minimum conditions and standards for fire safety relating to structures and exterior premises, including fire safety facilities and equipment to be provided.
      (2)   Responsibility. The owner of the premises shall provide and maintain such fire safety facilities and equipment in compliance with these requirements. A person shall not occupy as owner-occupant or permit another person to occupy any premises that do not comply with the requirements of this section.
   (b)   Means of egress.
      (1)   General. A safe, continuous, and unobstructed path of travel shall be provided from any point in a building or structure to the public way. Means of egress shall comply with the Florida Fire Prevention Code.
      (2)   Aisles. The required width of aisles in accordance with the Florida Fire Prevention Code shall be unobstructed.
      (3)   Locked doors. All means of egress doors shall be readily openable from the side from which egress is to be made without the need for keys, special knowledge, or effort, except where the door hardware conforms to that permitted by the Florida Building Code.
      (4)   Emergency escape openings. Required emergency escape openings shall be maintained in accordance with the code in effect at the time of construction, and the following. Required emergency escape and rescue openings shall be operational from the inside of the room without the use of keys or tools. Bars, grilles, grates or similar devices are permitted to be placed over emergency escape and rescue openings provided the minimum net clear opening size complies with the code that was in effect at the time of construction and such devices shall be releasable or removable from the inside without the use of a key, tool or force greater than that which is required for normal operation of the escape and rescue opening.
   (c)   Fire-resistance ratings.
      (1)   Fire-resistance rated assemblies. The required fire-resistance rating, of fire-resistance-rated walls, fire stops, shaft enclosures, partitions, and floors shall be maintained.
      (2)   Opening protectives. Required opening protectives shall be maintained in an operative condition. All fire and smoke-stop doors shall be maintained in operable condition. Fire doors and smoke barrier doors shall not be blocked or obstructed or otherwise made inoperable.
   (d)   Fire protection systems.
      (1)   General. All systems, devices and equipment to detect a fire, actuate an alarm, or suppress or control a fire or any combination thereof shall be maintained in an operable condition at all times in accordance with the Florida Fire Prevention Code.
      (2)   Smoke alarms. Single or multiple-station smoke alarms shall be installed and maintained in all multi-unit dwellings regardless of occupant load at all of the following, locations:
         a.   On the ceiling or wall outside of each separate sleeping area in the immediate vicinity of bedrooms.
         b.   In each room used for sleeping purposes.
         c.   In each story within a dwelling unit, including basements and cellars but not including crawl spaces and uninhabitable attics. In dwellings or dwelling units with split-levels and without an intervening door between the adjacent levels, a smoke alarm installed on the upper level shall suffice for the adjacent lower level provided that the lower level is less than one full story below the upper level.
   Single or multiple-station smoke alarms shall be installed in other groups in accordance with the Florida Fire Prevention Code.
      (3)   Power source. In all multi-unit dwellings, single-station smoke alarms shall receive their primary power from the building wiring provided that such wiring is served from a commercial source and shall be equipped with a battery backup. Smoke alarms shall emit a signal when the batteries are low. Wiring shall be permanent and without a disconnecting switch other than as required for over-current protection.
      Exception: Smoke alarms are permitted to be solely battery operated in buildings where no construction is taking place, buildings that are not served from a commercial power source and in existing areas of buildings undergoing alterations or repairs that do not result in the removal of interior wall or ceiling finishes exposing the structure, unless there is an attic, crawl space or basement available which could provide access for building wiring without the removal of interior finishes.
      (4)   Interconnection. Where more than one smoke alarm is required to be installed within an individual dwelling unit in Group R-2, R-3, R-4 and in dwellings not regulated as Group R occupancies, the smoke alarms shall be interconnected in such a manner that the activation of one alarm will activate all of the alarms in the individual unit. The alarm shall be clearly audible in all bedrooms over background noise levels with all intervening doors closed.
      Exceptions: Interconnection is not required in buildings which are not undergoing alterations, repairs, or construction of any kind. Smoke alarms in existing areas are not required to be interconnected where alterations or repairs do not result in the removal of interior wall or ceiling finishes exposing the structure, unless there is an attic, crawl space or basement available which could provide access for interconnection without the removal of interior finishes.
(Ord. No. 08-031, § 3, 11-18-08)
Loading...