(A) All multi-family dwelling units, motels, hotels, boarding houses, sleeping room houses, mobile home rentals, and buildings of mixed occupancy having any residential units located in the town shall be equipped with approved smoke detectors.
(B) Every owner, manager, or agent of any multiple dwelling shall install in every dwelling unit not less than one approved smoke detector on the ceiling, not less than seven inches from any wall or on a wall located from six to 12 inches from the ceiling and within 15 feet of all rooms used for sleeping purposes.
(1) Smoke detectors shall be mounted on the ceiling or wall at a point centrally located in the corridor or area giving access to the rooms used for sleeping purposes.
(2) Where a common hallway is used, smoke detectors shall be spaced not more than 30 feet apart in such hallway.
(C) The provisions of this section shall not be required in buildings which contain an approved automatic sprinkler system throughout.