907.6.7 FACP Location and Identification. The fire alarm control panel (FACP) shall be mounted in such a location to be in obvious view from the main entrance of the building.
Exception: When the FACP is not in obvious view, a remote annunciator shall be provided at the main entrance of the building and approved signage shall be installed to indicate the location of the FACP.
(Ord. 48-20, 12-8-2020, eff. 1-1-2021)