5-12-32: IFC AMENDMENT, ADD SECTION 901.4.2.1, NON- REQUIRED FIRE ALARM SYSTEMS:
   901.4.2.1 Non-Required Fire Alarm Systems. Non-required fire alarm systems shall be provided with occupant notification in accordance with the requirements of Section 907.5 for a required system. Partial coverage initiating devices shall be permitted provided the devices are installed in accordance with Section 907.4. Partial coverage occupant notification shall not be permitted unless specifically allowed in another section of this code.
(Ord. 48-20, 12-8-2020, eff. 1-1-2021)