9-1A-69: IBC BUILDING CODE AMENDMENT, APPENDIX H SIGNS, SECTION H104, IDENTIFICATION IS DELETED IN ITS ENTIRETY:
H104 Identification. Deleted in its entirety.
(Ord. 44-17, 12-19-2017, eff. 1-1-2018; amd. Ord. 39-20, 12-1-2020, eff. 1-1-2021)
9-1A-70: IBC BUILDING CODE AMENDMENT, APPENDIX H SIGNS, SECTION H105.1, GENERAL REQUIREMENTS, ADD EXCEPTION:
   H105.1 General Requirements. Signs shall be designed and constructed to comply with the provisions of this code for use of materials, loads, and stresses.
      Exception: Where Chapter 17 Special Inspections and Tests requires periodic special inspections for all post-installed concrete anchors, installation of signs utilizing these types of anchors will be considered minor in nature and not require periodic special inspection when acting primarily in shear and utilizing less than 50% of the allowable loading when tested in accordance with ACI 318.
(Ord. 44-17, 12-19-2017, eff. 1-1-2018; amd. Ord. 39-20, 12-1-2020, eff. 1-1-2021)
9-1A-71: IBC BUILDING CODE AMENDMENT, APPENDIX H SIGNS, SECTION H105.2, PERMITS, DRAWINGS AND SPECIFICATIONS:
   H105.2 Permits, drawings, and specifications. Where a permit is required, as provided in Chapter 1, construction documents shall be required. These documents shall show the dimensions, material, and required details of construction, including loads, stresses, and anchors. Plans and documents shall be submitted and include information as required by the applicable Boise City submittal checklist.
(Ord. 44-17, 12-19-2017, eff. 1-1-2018; amd. Ord. 39-20, 12-1-2020, eff. 1-1-2021)
9-1A-72: IBC BUILDING CODE AMENDMENT, APPENDIX H SIGNS, ADD SECTION H105.2.1, ENGINEERING:
   H105.2.1 Engineering. Submittal documents must include structural drawings and structural calculations stamped and signed by an Idaho licensed engineer.
      Exception: Engineering is not required for wall signs mounted flush against the wall with anchorage that can easily be verified as adequate.
(Ord. 44-17, 12-19-2017, eff. 1-1-2018; amd. Ord. 39-20, 12-1-2020, eff. 1-1-2021)
9-1A-73: IBC BUILDING CODE AMENDMENT, APPENDIX H SIGNS, SECTION H106.1, ILLUMINATION, AND ADD EXCEPTION:
   H106.1 Illumination. A sign shall not be illuminated by other than electrical means, and electrical devices and wiring shall be installed in accordance with the requirements of NFPA 70, National Electrical Code, and the International Energy Conservation Code. Any open spark or flame shall not be used for display purposes unless specifically approved by the building official and/or fire code official.
      Exception: Replaced signs on existing branch circuits do not need to comply with the controls of the Energy Conservation Code of Boise City when approved by the Electrical Inspection Supervisor or designee.
(Ord. 44-17, 12-19-2017, eff. 1-1-2018; amd. Ord. 39-20, 12-1-2020, eff. 1-1-2021)
9-1A-74: IBC BUILDING CODE AMENDMENT, APPENDIX H SIGNS, SECTION H106.2, ELECTRICAL SERVICE, AND ADD EXCEPTION:
   H106.2 Electrical service. Signs that require electrical service shall comply with NFPA 70, National Electric Code, and the International Energy Conservation Code.
      Exception: Replaced signs on existing branch circuits do not need to comply with the controls of the Energy Conservation Code of Boise City when approved by the Electrical Inspection Supervisor or designee.
(Ord. 44-17, 12-19-2017, eff. 1-1-2018; amd. Ord. 39-20, 12-1-2020, eff. 1-1-2021)
9-1A-75: IBC BUILDING CODE AMENDMENT, APPENDIX H SIGNS, SECTION H107.1.2, ELECTRIC SIGN FACES IS DELETED:
H107.1.2 Electric Sign Faces. Deleted.
(Ord. 44-17, 12-19-2017, eff. 1-1-2018; amd. Ord. 39-20, 12-1-2020, eff. 1-1-2021)